Catálogo fusibles SIBA 2022

URT

URT

5. Applications 5.1 SIBA U ltra- R apid Fuse Links In Rectifier Circuits The most common rectifier circuits are shown in table 5.1. The operating currents and operating voltages are coordinated with the individual circuits. Given are the coefficients for: • Operating current of a phase fuse link as a multiple of the D.C. load current. • Operating current of a fuse link placed at the inverter branch as a multiple of the D.C. load current. • Maximum value of the rectifier voltage as a multiple of the transformer voltage. • Operating voltage of the fuse link as a multiple of the floating voltage.

Fusing Location

Circuit Phase

Type

Code

Branch U AC /U 2

I RMS /I DC

I RMS /I DC

U fuse /U DC

Single Phase

1.00

0.50

1.41



Phase Full Wave Single Single Phase Half Wave

M1

1.57

1.57

1.41

2.22

M2

0.71

0.71

2.83

2.22

Single Phase

B2

1.00

0.71

1.83

1.11

Six Phase

M6

0.41

0.41

2.50

1.48

Six Phase

B6

0.82

0.58

2.50

0.74

Six Phase SD6

0.29

0.29

2.50

1.48

Twelve Phase SD12

0.14

0.14

2.50

1.48

Fig. 5.1 Cont. - Circuits for power semiconductors and appropriate calculation coefficients

portal: www.siballc.net e-mail: info@sibafuse.com

200

Made with FlippingBook - Online magazine maker