URDC-PV
URDC-PV
Rated Breaking Test
Class
UL 249-19 IEC 60269-6 Standard(s) VDE 0636-6
Rated Voltage
[U n ]
Capacity
gPV
Voltage
1000V DC
30kA @ L/R = 2ms 1000V DC
NH1
UL File E341342
current Rated
With
Pre-arcing
Power
Total
indicator
loss
I 2 t
I 2 t*
I n
@ I n [W]
@1000V DC
[A 2 s]
6 000 13 000 19 600 30 300 2 600 1 500 [A 2 s]
[A]
Article Number
414 740
63 80
2055629.100 2055629.125 2055629.63 2055629.80 2055629.160 2055629.200
21 19 17 14 32 27
200 160 125 100
1 700 3 700 5 600 9 900
* L/R = 2ms
Coefficients for Heavy Duty Applications
B1 max
A2
B2 0.5
a
0.8 Cf3
0.8 1.25
130
Dimensions [in /mm]
indicator
a5
2.03 / 51.5 1.65 / 42 0.24 / 6 0.55 / 14 2.56 / 65 5.31 / 135 0.79 / 20 1.57 / 40
c1 e1 e2 a5 a1 e4 b1
c1
b1
e1
f
e4
a1
f
e2
Accessories
Article Number Page
Article Description
Article Description
Page
Article Number
2155628 2800204 2800202
Microswitch (red hammer)Standard level (UL File E309038) Low level
540 547
Fuse base
Grip handle, insertion / removal tool
portal: www.siballc.net e-mail: info@sibafuse.com
313