URDC-PV
URDC-PV
Rated Breaking Test
Class
Standard(s) I EC 06269-6 VDE 0636-6 acc. UL 248-19
Rated Voltage
[U n ]
Capacity
gPV
Voltage
1000V DC
30kA @ L/R = 2ms 1000V DC
NH3
With
Pre-arcing
Total
Power
current Rated
indicator
loss @ I n
I 2 t
I 2 t*
I n
@1000V DC
[A 2 s] 33 000 64 000 40 000
[A 2 s]
2056829.315 Article Number 2056829.350 2056829.400
[A]
[W]
315 350 400
48 41 50
208 000 130 000 107 000
* L/R = 2ms
Coefficients for Heavy Duty Applications
B1 max 1.25
0.8 Cf3
a
0.8 A2
0.5 B2
130
Dimensions
indicator
[in /mm]
a5
e4 e1 e2 c1 a1 a5
5.91 / 150
2.56 / 65 b1 1.26 / 32
0.24 / 6 2.87 / 73 2.87 / 73 2.36 / 60 0.63 / 16
c1
b1
e1
f
f
e4
a1
e2
Accessories
Article Description
Article Number
Article Number
Article Description
Page
Page
2800204 2800202 2156828
Microswitch (red hammer)Standard level (UL File E309038) Low level
548 540
Fuse base
Grip handle, insertion / removal tool