UR-Acc
Standard(s) UL 4248-1 CSA 22.2 IEC 60269-1 & 2 60947-1 & 3
Rated Voltage 1000V DC - UL / IEC
Accessories
690V AC - IEC
w/lamp indicator or w/microswitch
UL File E186970 / CSA 262029 IEC
5105805DC Series for 14x51mm Fuse Links Fuse Modules
UL rec
5105805.2LDC 5105805.1LDC 5105805.1SDC* 5105805.2DC Article No. 5105805.1DC
Description
14x51mm DIN Rail Mounting Rated voltage; 1000V DC -* UL(rec), 1000V DC / 690V AC - IEC Rated current; 50A UL, 50A IEC Power acceptance; 6W Utilization Category AC-21B 690V AC , DC-20B 1000V DC Rated insulation voltage; U imp = 8kV Contacts; copper-silver plated Conductor solid; 1.5mm 2 -35mm 2 Conductor stranded; 1.5mm 2 - 25mm 2 , with or without ferrules Maximum torque; 2.5N•m - 3N•m Degree of protection; IP-20 ** (cable size < 10mm 2 contact SIBA) Pollution degree; 3 Construction, body & handle; Thermoplastic polyester Flammability "UL 94"; V0 Rating of indicator 350V DC -1000V DC Storage and operating temperature range; - to Handling of lever during installation and maintenance below -20°C must be avoided. Do Not Open Under Load ** Depends on connection and mounting parts
No indicator W/ neon lamp indicator W/ microswitch No indicator W/ neon lamp indicator
1-Pole
2-Pole
* UL only
1000V DC / 50A
Microswitch making and breaking capacity according to EN/IEC 60947.5.1 (6000 cycles)
Utilization category
48V
24V
380 / 440V
110 / 127V
220 / 240V
480V
AC-12
5A
5A
5A
5A
5A
5A
2A
0.4A
0.2A
DC 12
5A
Fuse module current de-rating for adjacent poles with direct contact Number De-rating of poles factor 1 - 4 1XI n 5 - 6
0.8XI n 0.7XI n 0.6XI n
7 - 9
10
5105805.1SDC*
IEC
portal: www.siballc.net e-mail: info@sibafuse.com
558