Catálogo fusibles SIBA 2022

UR-Acc

Standard(s) UL 4248-1 IEC 60269-1 & 2 IEC 60947-1 & 3

Rated Voltage 750V AC - UL

Accessories

690V AC / 750V DC - IEC

w/lamp indicator

UL File E186970

Fuse Modules

5105805 Series for 14x51mm Fuse Links

5105805.1S 5105805.1L 5105805.1 Article No. 5105805.3L 5105805.3 5105805.2 5105805.2L 5105805.2S 5105805.3S

Description

14x51mm DIN Rail Mounting Rated voltage; 750V AC UL(rec), 690V AC / 750V DC IEC Rated current; 50A UL, 50A IEC Power acceptance; 5W Peak withstand current; 200kA -UL 4248, 120kA IEC 60269 Conductor solid; 1.5mm 2 - 35mm 2 , Conductor stranded; 1.5mm 2 - 25mm 2 , with or without ferrules Maximum Torque; 2.5N•m - 3N• m Utilization Category AC 21B 690V AC , AC-22B 500V DC Pollution degree; 3 Rated insulation voltage; U imp = 8kV Degree of protection; IP-20**, consult SIBA flexible wire  10mm 2 solid wire  16mm 2 Contacts; copper-silver plated Flammability "UL 94"; V2 Construction, body & handle; Thermoplasticpolyester Operating and storage temperature range;     to    Handling of lever during installation and maintenance below -20°C must be avoided. Do Not Open Under Load

W/ microswitch No indicator W/ neon lamp indicator W/ microswitch No indicator W/ neon lamp indicator W/ microswitch No indicator W/ neon lamp indicator

1-Pole

2-Pole

3-Pole

Rating of light indicator; 230V AC/DC - 750V AC/DC , ** Depends on connection and mounting parts

750V AC / 50A

220 / 240V 380 / 440V 480V Microswitch making and breaking capacity according to EN/IEC 60947.5.1 (6000 cycles) Utilization 24V 48V 110 / 127V

category AC-12

5A

5A

5A

5A

5A

5A

DC 12

5A

2A

0.4A

0.2A

Fuse module current de-rating for adjacent De-rating poles with direct contact

of poles Number

factor

1XI n

5 - 6 1 - 4 7 - 9

0.8XI n 0.7XI n 0.6XI n

10

portal: www.siballc.net e-mail: info@sibafuse.com

560

Made with FlippingBook - Online magazine maker