NH aM
Rated Voltage Rated Breaking Test
Class
NH
Standard(s)
[U n ]
aM
Capacity
Voltage
DIN 43620 Part 5 VDE 0636 Part 2011
1000V AC
Live Metal Removal Tags 25kA - 00M / 63kA - 00M 760V AC
000M & 00M
Size 00M
Size 000M W/ Top Indicator
Rated Current
Pre-arcing I 2 t
Total I 2 t
Power Loss
W/ Top Indicator
I n
@ 760Vac [A 2 s] 2 100
[A 2 s]
[A]
Article Number
Article Number
8.0 3.5 5.8 2.1 2.5 1.8 0.9 1.3 [W]
16 20 25 35
2038608.16 2038608.20 2038608.25 2038608.35 2038608.63 2038608.80 2038608.100 2038608.50
520 930
5 800 3 700
1 450 2 450 5 500
9 800 22 000 42 000 52 000 76 000 120 000 212 000
125 160 50 63 80 100
10 500 13 000 19 000 30 000 53 000
2038908.125 2038908.160
13 17
Weight [kg per 1]
0.18
0.28
Units per Package
3
Dimensions [in / mm]
a 5 b 1 c 1 e 1 e 2 e 4 f a 1
4.61 / 117 3.35 / 85 1.26 / 15 1.38 / 35 1.16 / 29.5 0.24 / 6 0.54 / 13.5 1.80 / 46
4.33 / 110 3.07 / 78 1.02 / 15 1.38 / 35 1.60 / 40.5 0.80 / 20.5 0.24 / 6 0.28 / 7
indicator
a5
c1
b1
e1
f
e4
a1
e2
NH000 and NH00
Accessories
Article Description
Article Description
Article Number
Article Number
Page
Page
Microswitch (red hammer)
Fuse base 1-Pole, NH00 Fuse base 1-Pole, NH00C
2800202
596
2138601 2138901
603
Grip handle, insertion / removal tool
Standard (NH000-NH3)
2203101 2203102
604
W/ leather sleeve (NH000-NH3)
portal: www.siballc.net e-mail: info@sibafuse.com
589