Air flow resistance calculation Hot air ducting

In order to ensure a correct application with correct air ducting system, a continuous main line with openings that cannot be closed must be ensured. When branches are used, the lines branching off the main line are not taken into account. As a result, the branches can also be designed in a way to be closed. The following table lists several air ducting parts. The sum of resistance points must not exceed the maximum number of resistance points for each air heating model.

Air Top 2000 STC (325 P)

Air Top Evo 40 (550 P) / Air Top Evo 55 (375 P)

60 mm inlet

90 mm inlet

Dim. in mm

Id.

Dim. in mm

Id.

Intake grill / grille

60

1320163

90

1310581

Flexible tubing per meter

60

various

90

various

Elbow in flexible tube

60

various

90

various

Reducing adapter

90 >80

1320925

Hose connector

60

1320469

90

1319869

Elbow in flexible tube

90

1320706

Branch

60 / 60 / 60

1320472

90 / 60 / 90

1320707

D2a

D1a

D1a

L

80 / 55 / 55

1320753

Y-piece

80 / 60 / 60

1320471

90 / 90 / 90

1320470