Brahm Plug & Play Central Collector Series User Manual

F IRE S UPPRESSION F UNCTIONS

The functions of the fire suppression system (FSS) are driven by the Smart Relay. Heat and smoke

sensors internal to the unit are used for fire detection, and the system can be activated manually

through the fire pull. The system behaves as follows:

If:

Then:

The Key Switch is turned OFF

The fire suppression system is deactivated

(Key will be retained)

The motor/VFD will shut down immediately, valve pulsing is shut down immediately, louver closes immediately, alarm/strobe will activate immediately, and the fire bottle is triggered after a 20 second delay. The motor/VFD will shut down immediately, valve pulsing is shut down immediately, louver closes immediately, alarm/strobe will activate immediately, and the fire bottle is triggered after a 20 second delay. The motor/VFD will shut down immediately, valve pulsing is shut down immediately, louver closes immediately, alarm/strobe will activate immediately, and the fire bottle will NOT be triggered. The motor/VFD will shut down immediately, valve pulsing is shut down immediately, louver closes immediately, alarm/strobe will activate immediately, and the fire bottle is triggered after a 20 second delay. The motor/VFD will shut down immediately, valve pulsing is shut down immediately, louver closes immediately, alarm/strobe will activate immediately, and the fire bottle is triggered immediately.

The Fire Pull is activated

The Primary Heat Sensor is

triggered

(Valve Compartment)

The Smoke Sensor is triggered

(Valve Compartment)

The Secondary Heat Sensor is

triggered

(Filter Compartment)

Fire detector hose burst/Fire

Pressure Switch is triggered

Note : Fire bottle changed to ABC dry chemical or FM200.The default is the dry chemical unless

specially requested.

Page 24

sales@clean-air.com

clean-air.com

1-866-665-1829

Made with FlippingBook Annual report maker