FSS C OMPONENTS

Key Switch

NOTE: The system can only be deactivated while the power is off. The key switch will not function

once power to the panel has been turned on using the Disconnect.

The key switch is located on the front of the electrical door, and it is a retentive key switch. This

means while the system is turned off, the key cannot be removed. It is recommended that the key be

removed when the fire suppression system is active as a visual check. The fire suppression system

can only be deactivated when the power to the electrical disconnect is off. Once the power is on and

the key has activated the fire suppression system, the system will not turn off even if the key switch is

activated. The key switch is wired fail safe so that if the wires are removed or cut, the fire suppression

system is activated.

The fire suppression system can be deactivated using the key switch. When changing the filters in the

system per proper maintenance, dust can be dropper through cads and below the filter compartment.

This dust can then trigger the smoke sensors in the valve compartment. To prevent this, it is

recommended that the fire suppression be turned off using the key switch for several minutes upon

restarting the system after a filter change. After several minutes, the fire suppression can be

reactivated while the system is still running (it need not be restarted again). This process is only

necessary after filter changes, not on all startups.

If the key switch has been activated(FSS is deactivated) , the display will show “FSS OFF”

Page 25