Fire Pull
The fire pull is used for the manual activation of the fire suppression
system. The fire pull will be mounted on the front of the electrical door. A
key is used to reset the fire pull once it has been activated, and a glass
tube can be inserted to detect an activation that has been reset.
To reset the fire pull, the power must be turned off before the fire pull has
been reset. The internal program of the Smart Relay latches shut
electronically, forcing the power to be cycled off and then on. If the fire pull
has been activated, the display will show “FPull” as shown in the picture
below.
NOTE: The fault must also be cleared on the HMI by pressing the “FSS
Reset ” button on the fire suppression screen.
Page 26
sales@clean-air.com
clean-air.com
1-866-665-1829
Made with FlippingBook Annual report maker