Fire Pull

The fire pull is used for the manual activation of the fire suppression

system. The fire pull will be mounted on the front of the electrical door. A

key is used to reset the fire pull once it has been activated, and a glass

tube can be inserted to detect an activation that has been reset.

To reset the fire pull, the power must be turned off before the fire pull has

been reset. The internal program of the Smart Relay latches shut

electronically, forcing the power to be cycled off and then on. If the fire pull

has been activated, the display will show “FPull” as shown in the picture

below.

NOTE: The fault must also be cleared on the HMI by pressing the “FSS

Reset ” button on the fire suppression screen.