Brahm Plug & Play Central Collector Series User Manual

Secondary Heat Sensor

The heat sensor is located on back wall of the filter

compartment. This is the divider panel between the filter

compartment and the motor/valve compartments. It should

be visible between the first and second rows of filters without

removing the filters. For indoor units, the sensor is activated

if the temperature reaches 135 o F. For outdoor units, the sensor is activated if the temperature reaches 190 o F. It can

be tested using a heat gun directed towards the sensor.

If airflow is present the heat sensors and smoke sensors in

the valve compartment will be activated sooner. A signal is

sent to the controller to activate the rest of the fire

suppression system.

To reset the secondary heat sensor, the power must be

turned off and the sensor must be allowed to cool. The

internal program of the controller latches shut electronically, forcing the power to be cycled off and then

on. If the primary heat has been activated, the display will show “Heat2” as shown in the picture below.

Heat Detection Tubing

Heat Detection Tubing is a new fire detection system implemented by Clean Air Industries since January 2020. The tubing runs along the wall in the filter compartment. When temperature reaches 375 o F, the

tube bursts and immediately releases the fire suppression agent. The heat detection tubing is

implemented to allow the system to release the fire suppression agent even during power loss. The heat

detection tubing comes with pressure switch to monitor whether the fire suppression agent has been

released.