Brahm Plug & Play Central Collector Series User Manual

FSS Pressure Switch

The pressure switch monitors the pressure in the heat

detection tube. When the tube bursts, the pressure in

the tube will drop. This triggers the pressure switch,

which will then send signal to the PLC to let the PLC

know that the fire suppression agent has been released.

The fire suppression agent can also be actuated

electrically, when the fire pull is triggered, or when either

the primary or secondary heat detector detects heat

before the heat detection tubing melts.

Louvers

The louvers are located on top of the unit on the

intake and exhaust. They are pneumatically

controlled using solenoid valves. Activation of the

valve opens the louvers, deactivation closes. There

are indicator lights on the DIN connectors for the

valves to show if power is present or not.

The louvers are opened and shut using a pneumatic

cylinder. The cylinder has a spring extension so that

the loss of power will force the louvers shut. Check

valves are in place so that if compressed air is lost or

low, the louvers will not shut blocking air flow to the

unit. Compressed air is not required to close the louvers, only to open them due to the spring extension.

The door is sealed using bubble gasket. The seal is only to block air flow, and is not necessarily a 100%

seal.

The louvers close to prevent airflow when the fire suppression system is activated. On multi-module units,

louvers are used for each intake and exhaust.