Brahm Plug & Play Central Collector Series User Manual

Table 1:

IF:

THEN:

The Key Switch is turned OFF (key

The fire suppression system is deactivated.

will be retained)

The Fire Pull is activated

The motor/VFD will shut down immediately, valve pulsing is shut down

immediately, fire flap door closes immediately, alarm/strobe will activate

immediately, and the fire bottle is triggered after a 20-second delay.

The Primary Heat Sensor is

The motor/VFD will shut down immediately, valve pulsing is shut down

triggered (Valve Compartment

immediately, fire flap door closes immediately, alarm/strobe will activate

immediately, and the fire bottle is triggered after a 20-second delay.

The Smoke Sensor is Triggered

The motor/VFD will shut down immediately, valve pulsing is shut down

(Valve Compartment)

immediately, fire flap door closes immediately, alarm/strobe will activate

immediately, and the fire bottle will NOT be triggered.

The Secondary Heat Sensor is

The motor/VFD will shut down immediately, valve pulsing is shut down

triggered (Filter Compartment)

immediately, fire flap door closes immediately, alarm/strobe will activate

immediately, and the fire bottle is triggered after a 20-second delay.

Page 34