Table 1:
IF:
THEN:
The Key Switch is turned OFF (key
The fire suppression system is deactivated.
will be retained)
The Fire Pull is activated
The motor/VFD will shut down immediately, valve pulsing is shut down
immediately, fire flap door closes immediately, alarm/strobe will activate
immediately, and the fire bottle is triggered after a 20-second delay.
The Primary Heat Sensor is
The motor/VFD will shut down immediately, valve pulsing is shut down
triggered (Valve Compartment
immediately, fire flap door closes immediately, alarm/strobe will activate
immediately, and the fire bottle is triggered after a 20-second delay.
The Smoke Sensor is Triggered
The motor/VFD will shut down immediately, valve pulsing is shut down
(Valve Compartment)
immediately, fire flap door closes immediately, alarm/strobe will activate
immediately, and the fire bottle will NOT be triggered.
The Secondary Heat Sensor is
The motor/VFD will shut down immediately, valve pulsing is shut down
triggered (Filter Compartment)
immediately, fire flap door closes immediately, alarm/strobe will activate
immediately, and the fire bottle is triggered after a 20-second delay.
Page 34