NEW
AIR CONDITIONING TECHNOLOGY
ACTUATOR ‘STELLA’ 230 V NC FOR AUTOMATIC HYDRAULIC COMPARISON
TECHNICAL DATA
APPLICATION
Operating voltage:
230 V~, 50 Hz
‘Stella’ – the intelligent autonomous 230 VAC NC electrothermal actuator for automatic adaptive hydraulic balancing of heating manifolds’ heating circuits in surface heating and surface cooling systems. Sensors on the supply and return lines measure temperature differences, and an algorithm continuously calculates the necessary temperature spread and the appropriate valve position. Normally closed and features a folding lever for easily unscrewing the thermostat valve or opening it manually when it is disconnected from the mains. Features integrated inflow temperature limitation. Can be combined with all standard temperature controllers and terminal strips (except devices with triac switch- ing element).
Max. power consumption: Max. starting current:
30 W
approx. 0.13 A
Housing colour: Housing material:
grey-orange PA6 plastic 0 to 50 °C
Ambient temperature: Storage temperature: Permissible atmospheric humidity: Mounting / attachment:
−25 to +60 °C
Max. 95% rel. humidity, non-condensing
M 30 x 1.5
Protection rating: Protection class: Safety and EMC:
IP54
II
according to DIN EN 60730
Average power consumption: Opening / closing time:
approx. 1.7 W
approx. 3 min
Nominal stroke: Function type:
3.5 mm
normally closed
Nominal closing force:
110 N
Connecting cable:
1 m / 2 x 0.34 mm²
TYPE / IMAGE
ITEM NO.
FEATURES
CIRCUIT DIAGRAM
EURO / PG
ZBOOA-010.185
Actuator for automatic hydraulic balancing
G8990010
84.20 / I
SET 31
VV000046
Set for performing fully automatic hydraulic balancing consisting of 5 surface-mounted room thermostats, 1 terminal strip and 6 actuators.
798.70 / I
SET 32
VV000047
Set for performing fully automatic hydraulic balancing consisting of 5 flush-mounted room thermostats, 1 terminal strip and 6 actuators.
891.60 / I
ILLUSTRATIONS
BRIEF DESCRIPTION
§ Combinable with the commercial 2-point room temperature con- trollers (electromechanical, electronic, PWM), except devices with triac switching element § for heating and cooling systems § Features a folding lever for easily unscrewing the thermostat valve or opening it manually when it is disconnected from the mains § Temperature sensors suited for surface heating pipes made of plastic, metal or combinations thereof with an external diameter of 12 to 20 mm § measures a heating circuit’s outflow temperature § The range of setpoint temperatures Stella calculates is variable and dependent on user behaviour and the system’s environment § The valve can be adjusted to any desired position between OPEN and CLOSED and set to remain in that position. § An expansion element and a stroke measuring system are needed to position the valve stroke.
146
Catalogue 2025
Prices valid from 01.01.2025 – 31.12.2025, prices may be subject to change | V1
Made with FlippingBook Annual report maker