PRODUCT CATALOGUE 2024 | alre.de

PLANT ENGINEERING

UNIVERSAL CAPILLARY DOUBLE THERMOSTAT RTKSA CAPILLARY SYSTEM – TÜV-TESTED

TECHNICAL DATA

APPLICATION

Colour:

anthracite grey (similar to RAL 7016), front side transparent

This series of devices was specially developed for use in heating technolo- gy; in boiler systems or storage tanks; district heating transfer stations and heat transfer systems; in ventilation technology to monitor supply air or as limiters for electrical heating coils, as well as for controlling and monitoring temperatures in pipelines and tanks. Immersion sleeves, protection coils and mounting set JZ-31 for pipe mounting are not included in the scope of delivery.

Sensor material: Sensor length:

Cu

2 m

Max. sensor temperature: Max. head temperature: Permissible atmospheric humidity:

Top scale value +15%

80 °C

Max. 95% rel. humidity, non-condensing

Operating voltage:

none

Max. switching current:

NC contact: 16 (2.5) A at 230 VAC +10% 0.25 A at 230 VDC +10% NO contact TR / TW: 6.3 (2.5) A at 230 VAC +10% 0.25 A at 230 VDC +10% NO contact TB / STB: 2.0 (0.4) A at 230 VAC +10% 0.25 A at 230 VDC +10% Min. 100 mA at 24 V (AC / DC) 230 VAC 50 / 60 Hz, 230 VDC

Accessory JZ-30 must be used in conjunction with immersion sleeves.

Type testing by TÜV in accordance with DIN EN 14597

Min. switching current: Max. switching voltage: Min. switching voltage:

24 VAC / 50 Hz, 24 VDC

Switching element: Switching contact:

microswitch

2 x togglers, potential-free

Control range:

heating or cooling Push-in terminals

Electrical connection: Mounting / attachment:

Wall mounting or with optional process connection (immersion sleeve or protection coil)

Protection class: Protection rating:

I

RTKSA-xxx.x0x IP40 RTKSA-xxx.x1x IP54 IP65 (optional)

Safety and EMC:

In accordance with DIN EN 60730 (VDE 0631) liquid-filled capillary scale: degrees Celsius

Sensor:

General features:

CONTROL RANGE

TYPE

ITEM NO.

HYSTERESIS

SENSOR Ø X L

FEATURES

EURO / PG

RTKSA-010.200

KA001000 TR: 0 to 120 °C STB: 70 to 130 °C

TR: 3 K STB: -10 to -15 K*

6 x 87 mm 6 x 66 mm

TR (external setting), STB (internal setting / external reset) TW (internal setting) TB (internal setting / external reset)

143.00 / II

RTKSA-013.210

KA001200 TW: 0 to 120 °C TB: 20 to 150 °C

TW: 3 K TB: –10 to –15 K*

6 x 87 mm 6 x 55 mm

185.90 / II

RTKSA-014.210

KA001100 TW: 0 to 120 °C TW: 0 to 120 °C

TW: 3 K TW: 3 K

6 x 87 mm 6 x 87 mm

2x TW (internal setting)

143.00 / II

TR = temperature controller, TW = temperature monitor, TB = temperature limiter, STB = safety temperature limiter * Manual reset after cooling down by 10 – 15 K (depending on configured setpoint)

ACCESSORIES ITEM NO.

LENGTH

MATERIAL DIAMETER IXA**

FEATURES

EURO / PG

THK-2-100x17

KA979901 100 mm

nickel-plated brass 14.8 x 17 mm

Immersion sleeve

30.80 / II

THK-2-200x17

KA979902 200 mm

nickel-plated brass 14.8 x 17 mm

Immersion sleeve

41.30 / II

NTHK-2-100x17

KA979903 100 mm V4A (1.4571)

14.8 x 17 mm

Immersion sleeve

60.10 / II

NTHK-2-200x17

KA979904 200 mm V4A (1.4571)

14.8 x 17 mm

Immersion sleeve

62.30 / II

SWK-2-100

KA989901 100 mm

steel, nickel-plated 10.5 x 17 mm

Protection coil with flange plate

19.50 / II

SWK-2-200

KA989903 200 mm

steel, nickel-plated 10.5 x 17 mm

Protection coil with flange plate

24.90 / II

** I = minimum inner diameter / A = nominal outer diameter See page 231 for pictures and dimension diagrams for immersion sleeves/protection coils

172

Catalogue 2024

Prices valid from 01.01.2024 - 31.12.2024, prices may be subject to change | V1

Made with FlippingBook Annual report maker