PRODUCT CATALOGUE 2024 | alre.de

PLANT ENGINEERING

FROST PROTECTION THERMOSTAT JTF-1 – 25 CAPILLARY SYSTEM – 1 OR 2 STAGES – TÜV-TESTED – SWITCHING

TECHNICAL DATA

APPLICATION

Housing colour: Sensor material:

grey

Securing hot water registers against freezing. The frost protection thermostats JTF-21 to JTF-25 have 2 switch outputs that allow for intervention in the system before the critical point is reached. All the devices are intrinsically safe and offer a sealable setpoint configuration. The capillaries, with the exception of JTF- 3 / -4, are active over the entire length. The device gets actuated when about 30 cm of the capillary (or approx. 60 cm capillary in the case of 12-m variants) reach the defined value. JTF-1 to -25: For temperature measurement of non-ag- gressive gases. The mounting brackets JZ- 05 / 6 M (metal) or JZ-05 / 6 K (plastic) should be used for bracing the capillaries against the heat register. JTF-3 / -4 (additional application): The SW-200-12 protecting coil is to be used for temperature measurement of non-ag- gressive gases in the duct; for temperature measurement in non-aggressive fluids, the TH-140 immersion sleeve is to be used, and in aggressive fluids, the NTH-140 immersion sleeve.

Cu

Ambient temperature Permissible atmospheric humidity: Max. sensor temperature:

−10 to +55 °C

Max. 95% rel. humidity, non-condensing

200 °C

Operating voltage:

none

Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage:

15 (8) A 150 mA

JTF

230 V AC, 50 Hz 24 VAC, 50 Hz

Switching element: Switching contact:

microswitch

toggler, potential-free

Control range:

−10 to +12 °C

Electrical connection: Mounting / attachment:

screw-type terminals

wall mounting, controller housing must be fitted in such a way that it is not subjected to any temperature that is less than the scale value that has been set

Protection class: Safety and EMC:

I

JTF-..W

according to DIN EN 60730

Sensor:

gas-filled capillary, active over its entire length (except for JTF-3, JTF-3 W und JTF-4) intrinsic safety, scale: degrees Celsius

General features:

Note: Mounting flanges, immersion sleeves and protecting coils are not part of the delivery scope and must be ordered separately as accessories.

Type testing by TÜV in accordance with DIN EN 14597

JTF

CAPILLARY LENGTH

TYPE

ITEM NO.

FEATURES

EURO / PG

1-STAGE

JTF-1 *

E6090301

6.0 m

external setting, TR, IP40, hysteresis approx. 1 K

122.90 / II

JTF-1 / 12 *

E6090328

12.0 m

external setting, TR, IP40, hysteresis approx. 1 K

210.20 / II

JTF-1 W *

E6090014

6.0 m

internal setting, TW, IP65, hysteresis approx. 1 K

188.10 / II

JTF-2 **

E6090308

6.0 m

external setting, external reset, TB, IP 40, hysteresis: manual reset after temperature rise of approx. 4 K Internal setting, internal reset, TB, IP65, Hysteresis: manual reset after temperature rise of approx. 4 K external setting, TR, IP 40, hysteresis approx. 1 K, sensor dimensions: 9.5 x 76 mm, also for use in applications exposed to water internal setting, TW, IP 65, hysteresis approx. 1 K, sensor dimensions: 9.5 x 76 mm, also for use in applications exposed to water external setting, external reset, TB, IP 40, hysteresis: manual reset after temperature rise of approx. 4 K, sensor dimensions: 9.5 x 76 mm, also for use in applications exposed to water

139.70 / II

JTF-2 W **

E6090287

6.0 m

205.10 / II

JTF-3 *

E6090309

1.8 m

118.10 / II

JTF-3 W *

E6090065

1.8 m

183.00 / II

JTF-4 **

E6090310

1.8 m

132.80 / II

JTF-5 *

E6090311

3.0 m

external setting, TR, IP40, hysteresis approx. 1 K

119.40 / II

183

Catalogue 2024

Prices valid from 01.01.2024 - 31.12.2024, prices may be subject to change | V1

Made with FlippingBook Annual report maker