PRODUCT CATALOGUE 2024 | alre.de

PLANT ENGINEERING

DUCT THERMOSTAT JTU-1…-50 CAPILLARY SYSTEM – TÜV-TESTED

TECHNICAL DATA

APPLICATION

Housing colour: Sensor material:

grey

Minimum or maximum thermostat for inflow air monitoring and fan regulation in ventilation and air conditioning systems. Overheating protection thermostat for electrical heat registers and directly fired air heaters with oil and gas operation. Attention : Assemble the device in a vibration-free manner in order to avoid malfunctions and / or sensor rupture. JTU-20, -3: Type testing by TÜV in accordance with DIN EN 14597, for hot air heaters in accordance with DIN 4794

Cu

Ambient temperature: Permissible atmospheric humidity: Max. sensor temperature:

−15 to +80 °C

Max. 95% rel. humidity, non-condensing

200 °C

Operating voltage:

none

Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Electrical connection: Mounting / attachment:

15 (8) A 150 mA

230 V AC, 50 Hz 24 VAC, 50 Hz

microswitch

toggler, potential-free screw-type terminals mounting on air duct

Protection rating: Protection class: Safety and EMC:

IP40

I

according to DIN EN 60730

Sensor:

liquid-filled capillary, active over its entire length internal setting, scale: degrees Celsius

General features:

TYPE ITEM NO.

CONTROL RANGE

HYSTERESIS (AP- PROX.)

CAPILLARY LENGTH

FEATURES

EURO / PG

JTU-50

E6100000

−25 to +65 °C 1.5 K

350 mm

Control function: heating or cooling, TW

174.00 / II

JTU-1

E6100012

c

8–30 K adjustable

350 mm

Control function: heating or cooling, TW, intrinsic safety, protection against cold Control function: heating or cooling, locked when the temperature is rising, STB, intrinsic safety, protection against cold, overheating protection Control function: heating or cooling, locked when the temperature is rising, STB, intrinsic safety, protection against cold

203.30 / II

JTU-3

E6100036

20 to 100 °C

external reset

350 mm

177.90 / II

JTU-20

E6100075

20 to 100 °C

external reset

1250 mm

193.90 / II

JTU-5

E6100048

60 to 140 °C 8–30 K adjustable

350 mm

Control function: heating or cooling, TW

202.40 / II

JTU-6

E6100051

60 to 140 °C

external reset

350 mm

Control function: heating or cooling, locked when the temperature is rising, TB

175.60 / II

TW = temperature monitor, STB = safety temperature limiter, TB = temperature limiter

JTU-2 is replaced by JTU-3.

Intrinsic safety / protection against cold: The devices are intrinsically safe, i.e., upon loss of the sensor medium owing to sensor rupture, for example, the burner is switched off. Since minus temperatures generate the same effect through volume reduction of the sensor medium, the devices are adjusted by means of the ‘cold screw’ such that they switch off the burner only at temperatures below −15 °C. They can only be switched on again manually at temperatures above approx. –5 °C by means of the manual reset button. Overheating protection : This device provides protection from uncontrolled overheating, which is caused, for example, by a heat build-up or by creeping capillary filling losses when there is invisible damage to the sensor or the capillary tube etc. Upon reaching a temperature of 220 °C, the safety slot in the sensor melts and, in reaction to losing the filling medium, the device switches off the burner towards the safe side. The burner cannot be switched on again. The device is then unus- able and serves as evidence of the presence of an over-temperature of at least 220 °C.

Locking: For types JTU-3, JTU-6 and JTU-20, a restart after cooling down is only possible by manual reset.

188

Catalogue 2024

Prices valid from 01.01.2024 - 31.12.2024, prices may be subject to change | V1