xLadder user manual-V2.0.0.6

6.16 Timer

6.16.1 Switch on delay timer

Input/output Operand

Data type

Txxx

constant(T0 -T255)

word

IN

Enable bit

Boolean

PT

VW, IW, QW, MW, SW, SMW, LW, AIW, T, C, AC,constant, *VD, *LD, *AC integer

TON: When the value of the input “ IN ” is equal to 1,

timer starts time.Timer current value of Txxx is the

current time (a multiple of the time base).When the

current value of the timer is equal to the preset time (PT),

the value of the timer bit is 1.When the value of the

input “ IN ” is equal to 0, timer current value is cleared.

TON, TONR and TOF timers have three kinds of resolutions.Each current

value is a multiple of the time base.For example, the number 50 in the

10 millisecond timer is 500 milliseconds.

Timer range:

Time base ( ms ) Time range (s)

Timer number

T0

1

65.535

T1~T4

10

655.35

T5~T31

100

6553.5

T32

1

65.535

T33~T36

10

655.35

T37~T63

100

6553.5

T64

1

65.535

T65~T68

10

655.35

T69~T95

100

6553.5

T96

1

65.535

T97~T100

10

655.35

T101~T127

100

6553.5