UMB06
Write a single hold register
EN : enable or not enable
TBL:Configuration table,If the input is MB200: MB200 is the configuration word ( Instruction Output ) M200.0 Communications have been queued ( Instruction Output ) M200.1 Communication completion ( Instruction Output ) M200.2 Communication error ( Instruction Output ) MB201 is error number.0 indicates no error.
SLA : MODBUS slave address
ADDR : The offset of hold register ( The offset of 4X )
LDAT : Store the data which will be written to the slave station.
UMB16
Write more than one hold registers
EN : enable or not enable
TBL:Configuration table,If the input is MB200: MB200 is the configuration word
( Instruction Output ) M200.0 Communications have been queued ( Instruction Output ) M200.1 Communication completion ( Instruction Output ) M200.2 Communication error ( Instruction Output ) MB201 is error number.0 indicates no error.
SLA : MODBUS slave address
ADDR : The offset of hold register ( The offset of 4X )
CNT : Number of hold register LDAT : Store the data which will be written to the slave station. The use of MODBUS communication instructions will be illustrated with
examples in the additional chapter.
230