xLadder user manual-V2.0.0.6

10.2 Value range of analog quantity:

0~10v → 0~1000

0~20ma → 0~1000

4~20ma → 0~1000

-50 ℃ ~200 ℃ → -500~2000

When you use the PT100 module , The value range of the analog quantity is

-500~2000.It corresponds to the temperature that is -50 ℃ ~200 ℃ .

10.3 Extension module address

10.3.1 Digtal Input addressing

Divided into the following two situations:

1. Common I/O expansion, such as PR - E - 16DC - DA - R ① .

2. Pure input expansion, such as PR - E - DC - 16IN ② . The PR12N,18N,26N PLCs with firmware version number >=V150, the version of PR - 18DC - DA - R >=10 supports these newly added addresses.

LAD MODBUS ADD.

Input

FBD

LADDER

Modbus code: 02

I1 -- I8

I0.0 – I0.7

0 -- 7

CPU

I9 -- IG I1 – I8 I1 – I8 I9 -- IG I1 – I8 I1 – I8

I1.0 – I1.7 I2.0 -- I2.7

8 -- 15

16 -- 23

8DI ①

I21.0 -- I21.7 or I2.0 -- I2.7

5800 - 5807 or 16 - 23

EXT.1

16DI ②

I22.0 -- I22.7

5808 - 5815

24 -- 31

8DI

I3.0 -- I3.7

I23.0 -- I23.7 or I3.0 -- I3.7

5816 - 5823 or 24 - 31

EXT.2

16DI

I9 -- IG I1 – I8

I24.0 -- I24.7

5824 - 5831

32 -- 39

8DI

I4.0 -- I4.7

I1 – I8

I25.0 -- I25.7 or I4.0 -- I4.7

5832 - 5839 or 32 -- 39

EXT.3

16DI

I9 -- IG I1 – I8

I26.0 -- I26.7

5840 - 5847

40 -- 47

8DI

I5.0 -- I5.7

I1 – I8

I27.0 -- I27.7 or I5.0 -- I5.7

5848 - 5855 or 40 - 47

EXT.4

16DI

I9 -- IG I1 – I8 I1 – I8

I28.0 -- I28.7

5856 - 5863

48 -- 55

8DI

I6.0 -- I6.7

I29.0 -- I29.7 or I6.0 -- I6.7

5864 - 5871 or 48 - 55

EXT.5

16DI

I9 -- IG

I30.0 -- I30.7

5872 - 5879

239