xLadder user manual-V2.0.0.6

QoS Level: QoS 0(no answer) or QoS 1(answer). If you wish to receive a response from the MQTT server, select ‘QoS 1’. Publish interval time: Publish timer setting. If enabled, the xLogic will publish the message to the MQTT server every x seconds. If disabled, the message will only be sent once. Publish topic: Set when creating a new topic project on the MQTT server. Parameter : Set the message content.

Digital output. Indicates whether the information was successfully published. 0: Not triggered or failed to publish 1: Successfully publish data

Out 1

Analog output. Publish status code.

Out 2

0: Block is not triggered 2: Waiting for the MQTT server to connect 4: Time to time start send the published data to the server and wait for server. Response (QoS1).