2-wire ( short circuit M+ and Ic)
3 wire
3.4.2 Connecting xLogic Outputs 1. Requirement for the relay output
Various loads such as lamp, fluorescent tube, motor, contact, etc., can
be connected to the outputs of xLogic. The maximum ON output current that
can be supplied by xLogic is 10A for the resistance load and 3A for the
inductive load. The connection is in accordance with the following figure:
2. Requirement for the electronic transistor output:
The load connected to xLogic must have the following
characteristics:
* The maximum switch current cannot exceed 0.3A.
23