5-28
Selection Guide
APAX Series Selection Guide
APAX Analog I/O Module
Model
APAX-5013
APAX-5017
APAX-5017H
APAX-5018
APAX-5028
12-ch analog input module
12-ch high-speed analog input module
12-ch thermocouple module
8-ch analog output module
8-ch RTD module
Description
Dimensions (W x H x D) Power Consumption
30 x 139 x 100 mm
General
(typical) 4 W @ 24 V DC
(typical) 3.5 W @ 24 V DC
(typical) 3.5 W @ 24 V DC
(typical) 3.5 W @ 24 V DC
(typical)
2.5 W @ 24 V DC
8 (differential)
12 (differential)
12 (differential)
12 (differential) V, mV, mA, thermocouple
-
Channels
RTD (2-wire or 3-wire)
V, mV, mA
V, mV, mA
-
Input Type*
10 sample/second (total)**
12 sample/second (total)**
1,000 sample/second (per channel) 16-bit (accuracy: ±0.1% of scale range for voltage; ±0.2% of scale range for current)
12 sample/second (total)**
Sampling Rates
-
16-bit (accuracy: ±0.1% of scale range for voltage; ±0.2% of scale range for current)
16-bit (accuracy: ±0.1% of scale range for voltage; ±0.2% of scale range for current)
Analog Input
16-bit (accuracy: ±0.1% of scale range)
-
Resolution
2 MΩ (voltage), 120 Ω (current)
>1 MΩ (voltage), 120 Ω (current) (4 ~ 20 mA and thermocouple)
>10 MΩ (voltage), 120 Ω (current)
Input Impedance Wire Burnout Detection
-
>10 MΩ
-
(4 ~ 20 mA only)
(4 ~ 20 mA only)
14-bit (accuracy: ±0.1% of scale range)
-
-
-
-
Resolution
- -
- -
- -
- -
8
Channels
Analog Output
V, mA
Output Type*
0.7 V DC /µs (per channel)
-
-
-
-
Slew Rate
Operating Temperature Storage Temperature
-10 ~ 60°C (when mounted vertically)
-40 ~ 70°C
Environment
Relative Humidity
5 ~ 95% (non-condensing)
* Each channel can be configured with different type and range ** Sampling rate depends on used channel number. Example: Using 6 channels on APAX-5017, sampling rate for each used channel will be 12/6 = 2 samples/second.