Catálogo Maestro IIoT Advantech

7-16

Product Introduction

ADAM-4100 Series

Robust Remote Data Acquisition and Control Modules Overview

Applications ƒ ƒ Wide operating temperature: -40 ~ 85°C ƒ ƒ Higher Noise Immunity ESD (IEC 61000-4-2) 8KV EFT (IEC 61000-4-4) 4KV Surge (IEC 61000-4-5) 4KV ƒ ƒ Wide power input: 10 ~ 48 V DC ƒ ƒ Support modbus/RTU ƒ ƒ Multiple interface :RS-485, Micro USB

Introduction The robust ADAM-4000 family includes ADAM-4100 series modules, the ADAM-4510I, and the ADAM-4520I modules. The ADAM-4100 series comprises compact, versatile sensor- to-computer interface units designed for reliable operation in harsh environments. Their built-in microprocessors, encased in rugged industrial-grade PC plastic, independently provide intelligent signal conditioning, analog I/O, digital I/O, LED data display, and an address mode with a user-friendly design for convenient address reading. The ADAM-4510I and ADAM-4520I modules are robust industrial-grade communication modules. Designed for Harsh Industrial Environments ADAM-4100 Module with LED Display ADAM-4100 series modules have an LED display that lets you monitor the channel status. For the ADAM-4117 and ADAM-4118, the LED will be lit when the related channel is active; for the ADAM-4150 and ADAM-4168, the LED will be lit when the related channel value is high. ADAM-4100 series modules have two operating modes: initial and normal. In contrast to old modules that require additional wiring to set the mode, this can be done using a switch with ADAM-4100 modules, making it very convenient to configure. When set to initial mode, the LED display represents the node address of the module. Additionally, in systems where multiple ADAM-4100 series modules are used, you can locate individual modules using Adam/Apax .NET Utility and the LED display on the module. All of these functions are very helpful for diagnosing ADAM-4100 series systems. Online Firmware Updates ADAM-4100 series modules have a user-friendly and convenient design that allows for firmware updates via a local network or the Internet. You can easily update to the latest firmware using Adam/Apax .NET Utility on the host PC. This saves time and ensures that the module always runs with the latest functional enhancements.

Micro USB interface USB has become common interface in IoT devices, and it is easy to be accessed via PC. To expand the accessibility of ADAM-4100 series modules, in addition to an RS-485 serial port, the B version of these modules also has a micro USB interface that supplies power and a communication interface. Users have the option to use the RS-485 and USB ports concurrently or independently, depending on their application. The ADAM-4100 micro USB interface can be adapted to standard micro USB cable. Advantech also offers a 90° cable (optional) with a locking screwmechanism to further enhance the connection stability.

Access ADAM by Passive RFID There is a trend in current IoT applications where increasingly more data are needed. Consequently, the demand for I/O modules is increasing. Users are pursuing efficient ways to set up and manage the modules. Thus, how to deploy I/O modules quickly and trace related usage information to avoid downtime have become key requirements in IoT applications. To fulfill these needs, ADAM-4100 series modules (B version) implement a passive internal RFID tag. This remarkable feature means that module information such as the model name, device ID, I/O value, firmware version, alarm events, and serial number are stored in the RFID tag. In contrast to typical RFID tags that contain fixed data, the RFID tag information in ADAM modules can be dynamically updated, which means that the RFID tag will reflect the latest ADAM module information. This innovative design makes ADAM modules more flexible for IoT applications.

Customized 90 degrees designed cable (optional accessory)

One-to-Many Wireless Configuration

Always-On Wireless Inspection

USB

Micro USB

Made with FlippingBook - professional solution for displaying marketing and sales documents online