20250702 HV V1

Operations training

High Voltage Standard / V1 02072025

c.

how to establish an electrically safe work condition

ELEMENT 10.2 - APPLYING THE FIVE SAFETY RULES / THE GOLDEN FIVE

Learning objectives:

72) Apply the Five Safety Rules or Golden Five Rules to operate safely in HV environments (Skills, intermediate level)

The instructor shall:

Explain and demonstrate applying the Five Safety Rules or local equivalent to operate safely in HV environments:

1. Disconnect completely

2. Secure against re-connection

3. Verify absence of operating voltage

4. Carry out earthing and short-circuiting

5. Provide protection against adjacent live parts

Facilitate the participants to take part in series of desktop exercises simulating typical HV operations working scenarios. Participant must reflect on the task allocated and apply rules correctly based on:

a.

Five Safety Rules - EN50110-1

b.

The Golden Five - NFPA 70E

c.

or any local equivalent

Lead the class in an activity to prepare the steps of a simple Switching Schedule or Switching Sequence:

a.

applying the principles of the five safety rules

Ensure to use a simple operation for the activity and emphasise that a Switching Schedule is not a task within the normal role of the switching person in the workplace.

Note

Global Wind Organisation / www.globalwindsafety.org

48 / 120