GARN® WHS | Hydronic System Design Manual

EQUIVALENT FEET OF PIPE FOR PEX FITTINGS (brass fittings)

Nominal pipe size, inches

1/2

3/4

1

1 1/4

1 1/2

2

90 Degree Elbow

3.0 1.0 2.0 1.0

2.2 0.3 0.8 0.3

3.4 0.2 2.0 0.2

9.6 1.5 8.8 1.6

10.9

11.3

Coupling

2.7

1.4

Tee-Branch Flow

11.6

12.1

Tee-Line Flow

2.1

1.6

(EP fittings)

90 Degree Elbow

3.7 1.0 1.0 2.3

2.3 0.2 0.2 0.8

4.6 0.2 0.2 2.0

10.0

11.5

- - -

Coupling

-

-

Tee-Branch Flow

3.8 8.6

1.8

Tee-Line Flow

10.6

FLOW AND HEAT CAPACITY @ 4' OF HEAD LOSS PER 100' OF PIPE LENGTH

SIZE

INSIDE DIA.

FLOW, gpm

BTU/HR 10°F Δ T

BTU/HR 20°F Δ T

BTU/HR 30°F Δ T

Oxygen Barriered PEX Tubing

5/8” 3/4"

0.574” 0 .678” 0 .875” 1.280" 1.600" 2.030"

2.5

12,500 15,000 27,500 75,000 135,000 260,000

25,000 30,000 55,000 150,000 270,000 520,000

37,500 45,000 82,500 225,000 405,000 780,000

3

1"

5.5

1 1/4" 1 1/2"

15 27 52

2"

Type L Rigid Copper Tube - max. vel = 6'/sec for noise; max. vel = 10'/sec for erosion

3/4"

0.785" 1.025" 1.265" 1.505" 1.985"

3.5 6.5

17,500 32,500 60,000 90,000 195,000

35,000 65,000 120,000 180,000 390,000

52,000 97,000 180,000 270,000 585,000

1"

1 1/4" 1 1/2"

12 18 39

2"

Schedule 40 Black Steel Pipe

3/4"

0.824" 1.049" 1.380" 1.610" 2.067"

4.2

21,000 40,000 85,000 125,000 240,000

42,000 80,000 170,000 250,000 480,000

63,000 120,000 255,000 375,000 720,000

1"

8

1 1/4" 1 1/2"

17 25 48

2"

13

Hydronic System Design Manual ©DECTRA CORPORATION - March 2013

Made with FlippingBook - professional solution for displaying marketing and sales documents online