GARN® WHS | Hydronic System Design Manual

ZERO PRESSURE, FIXED SUPPLY TEMP – PRIMARY SECONDARY PUMPING:

A primary-secondary pumping scenario involves two pumps: The primary pump circulates water between the GARN unit and the heat distribution piping; the secondary pump circulates water through the heat distribution piping.

Advantages

Disadvantages

 The main advantage of this type of system is that it can be directly connected to an existing zero pressure heating system.  Temperature and flow can be controlled independently.  Primary loop pump only needs to be sized from the primary loop piping.  Secondary loop pump only needs to be sized for secondary loop piping.  No mixing valve required.  No expansion tank required.

 Cannot connect to a pressurized system.  If pumping to a level higher than the level of the GARN unit, the system will drain back to the GARN which could prevent many pipes from remaining “ wetted ” .

24

Hydronic System Design Manual ©DECTRA CORPORATION - March 2013