GARN® WHS | Hydronic System Design Manual

ROOM

AREA (sq. ft) FIN TUBE LENGTH (ft)

Eat in Kitchen 1-1/2 Baths 3 Bedrooms Living Room

204

10’

100 (total) 156 (each)

5’

8’ per room

280

14’

Hall

48

0’ (no load – internal)

Total

53’

Main Floor Flow Calculations

However, the minimum flow through any run of HWBB is typically = 1 gpm, with NO more than 20’ of HWBB in any single run. Therefore:

Kitchen: 10’ < 20’ = 1 gpm 1- 1/2 Bathrooms: 5’ < 20’ = 1 gpm Living Room: 14’ < 20’ = 1 gpm Bedrooms: 8’ each < 20’ = 1 gpm per bedroom (3 gpm total)

6 gpm total required

A radiant floor manifold can be used with HWBB or wall mounted panel radiators to provide for individually controlled zones. In this case each bedroom could be a single zone with the remainder of the main level a single zone for a total of 4 zones. See the following diagram:

Figure 1: Main Level Floor Manifold Schematic

Use wall-mounted thermostats with manifold mounted zone control valves with end switch.

42

Hydronic System Design Manual ©DECTRA CORPORATION - March 2013