GARN® WHS | Hydronic System Design Manual

BASEMENT LEVEL DESIGN:  Assume no carpet  1 zone radiant floor

From radiant floor manufacturer’s data:  Install radiant loops 12” on center 

The manufacturer chosen for this example recommends a maximum loop run of 300’ for ½” PEX. The maximum loop length varies from manufacturer to manufacturer and by pipe size. See “ Radiant Floor Heating ” section of this manual.  Average loop temperature required is 85°F  HWS = 90°F (for a bare, concrete floor)  ΔT = 10°F

Calculate the # of loops of ½” PEX:

[

]

Basement Flow Calculations:

[

]

SIZE THE MAIN FLOOR HOUSE PUMP Each HWBB section includes a 3/4 ” copper fin tube element. At 1 gpm, head loss for 3/4 ” copper is about 0.5’ per 100’ (see, “ Flow and Heat Capacity Tables ”) . The head loss for 1/2 ” PEX at 1 gpm is approximately 3 ’ per 100’ .

HWBB Loss

(

)

1/2 ” PEX

(

)

Radiant Manifold

2’

1” Copper Feed to Manifold

(

)

1” Mixing Valve

4’

Subtotal

8.31’ 10%

Misc Fittings

Total Head Loss 9.14’ Size the house pump for 6 gpm @ 9.14’

43

Hydronic System Design Manual ©DECTRA CORPORATION - March 2013