Control Techniques - Comprehensive Catalogue

WWW.CONTROLTECHNIQUES.COM

WWW.CONTROLTECHNIQUES.COM

SPECIFICATION

Reference standard IEC60068-2-27, IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test. Tested to Environmental Category ENV3.

Vibration

Frame 3 to 11 – Surface mount (supplied mounting brackets) or through-panel mount (optional mounting brackets). Frame 3 to 5 – Tile mount (optional mounting brackets)

Mounting methods

Feature

Description

Output frequency/speed range

599Hz (Open-loop), 560Hz (RFC-A, RFC-S)

Safety Information, Quality Certificate, Control signal connectors, 24V power supply connector (frames 6 to 11), Grounding bracket, Surface mounting brackets, DC connection grommets (frames 3 to 6), Supply and motor connectors (frames 3 to 5), Nuts for supply and motor terminals (frames 6 to 11)

Braking

In-built braking transistor for use with external braking resistor (all frames)

Items supplied with the drive

Open-loop: Open-loop vector, fixed V/F RFC-A: Rotor Flux Control for Asynchronous motors,with or without position feedback RFC-S: Rotor Flux Control for Synchronous motors,with or without position feedback

Operating modes

Storage temperature

-40°C to 55°C, -40°F to 131°F

Operating temperature without de-rate

-20°C to 40°C, -4°F to 104°F

Overload capability

Heavy duty: Open-loop 150% overload, RFC 175% overload with CT profile, RFC 200% max overload.

Operating temperature with de-rate

40°C to 55°C, 104°F to 131°F

Overvoltage category

Evaluated for Over Voltage Category III.

AC supply voltage: 200 V drive: 200 V to 240 V ±10 % 400 V drive: 380 V to 480 V ±10 % 575 V drive: 500 V to 575 V ±10 % 690 V drive: 500 V to 690 V ±10 % Number of phases: 3 Maximum supply imbalance: 2 % negative phase sequence (3 % voltage imbalance between phases). Frequency range: 45 to 66 Hz For UL compliance only, the maximum supply symmetrical fault current must be limited to 100 kA

Concentrations of corrosive gases must not exceed the levels given in: Table A2 of EN 50178:1998, Class 3C2 of IEC 60721-3-3 This corresponds to the levels typical of urban areas with industrial activities and/or heavy traffic, but not in the immediate neighbourhood of industrial sources with chemical emissions. IEC EN 61000-4-2 Electrostatic discharge IEC EN 61000-4-3 Radio frequency radiated field IEC EN 61000-4-4 Fast transient burst IEC 61000-4-5 Surges IEC EN 61000-4-6 Conducted radio frequency IEC EN 61000-4-11 Voltage dips, short interruptions & variations IEC EN 61000-6-1 Electromagnetic compatibility residential, commercial and light-industrial environments IEC EN 61000-6-2 Electromagnetic compatibility for industrial environments IEC 61800-3 Adjustable speed electrical power drive systems - Part 3: EMC requirements EN12016:2013 Electromagnetic compatibility standard for lifts, escalators and moving walks Immunity with the recommended external filters and line reactors. Meets requirements of Equipment Category C3, C4 without external filters or line reactors. Meets requirements of Equipment Category C2 with the recommended external filters and line reactors. IEC 61800-3 Electromagnetic compatibility (EMC) requirements for power drive systems IEC EN 61000-3-2 Electromagnetic compatibility - Limits for harmonic current emissions IEC EN 61000-3-3 Electromagnetic compatibility Limitation of voltage changes,voltage fluctuations and flicker in public low-voltage supply systems ≤ 16 A IEC EN 61000-3-11 Electromagnetic compatibility Limitation of voltage changes,voltage fluctuations and flicker in public low-voltage supply systems < 16 A < 75 A IEC EN 61000-3-12 Electromagnetic compatibility Limits for harmonic currents produced by equipment connected to public low-voltage systems > 16 A and ≤ 75 A per phase IEC EN 61000-6-4 Electromagnetic compatibility (EMC) Emission standard for industrial environments EN 12015:2014, Electromagnetic compatibility standard for lifts, escalators and moving walks Emmission with the recommended external filters and line reactors.

Corrosive environments

Supply requirements

Immunity Compliance

Switching frequency range

2,3,4,6,8,12,16kHz (Factory default = 8kHz Open-loop/RFC-A/RFC-S)

CE approval – Europe RCM regulatory compliance mark – Australia UL / cUL approval – USA & Canada RoHS compliant – Europe Functional safety – USA & Canada Eurasian conformity – Eurasia

Approvals

EN 61800-5-1:2016 Adjustable speed electrical power drive systems - Part 5-2: Safety requirements – Functional EN 61800-5-1:2016 (in extracts) Adjustable speed electrical power drive systems - Part 5-1: Safety requirements - Electrical, thermal and energy EN 61800-3: 2004+A1:2012 Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods EN ISO 13849-1:2015 Safety of Machinery, Safety-related parts of control systems, General principles for design EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 Safety of machinery, Functional safety of safety related electrical, electronic and programmable electronic control systems IEC 61508 Parts 1 - 7:2010 Functional safety of electrical/ electronic/programmable electronic safety-related systems

Emission compliance

Product safety standard

Altitude

1000m – No de-rate. 1000m to 3000m - 1% de-rate/100m

Cooling

Variable speed forced controlled heatsink cooling fans

Humidity

95% Non-condensing at 40 °C (104 °F)

Safe Torque Off

Single STO channel. SIL 3

Pollution

Degree 2. Dry, non-conducting pollution only

Onboard: RS485, Modbus/TCP SI Options: Ethernet, CANopen, DCP

Communications

IP20 / NEMA1 / UL TYPE 1 (UL open class as standard, additional kit needed to achieve Type 1) IP65 / NEMA4 / UL TYPE 12 rating on the rear of drive when through panel mounted (Frames 3 to 8) IP55 / NEMA4 / UL TYPE 12 rating on the rear of drive when through panel mounted (Frames 9 to 11)

IP Rating

3 x Analogue input (1 x differential, 2 x single ended), 2 x Analogue output, 3 x Digital I/O programmable, 3 x Digital input (including 2 x high speed – 250µs), 1 x NO relay 250Vac Max., 6 x 0V common, 1 x 24V supply input (additional digital input), 1 x 24V user output (additional digital output), 1 x 10V user output, 1 x Safe Torque Off input. Additional I/O also available with SI-I/O option module.

Control I/O

124

125