SPECIFICATION

Concentrations not exceeding levels set in: EN 50178:1998 Table A2 IEC 60721-3-3 Class 3C2

Corrosive environments

Immunity Compliance

IEC61800-3, EN60800-6-2, IEC 61000-4-2, IEC 61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6,

F600

IEC61000-4-11, IEC61000-6-1, IEC 61000-6-2.

Step-By-Step Guide, safety information, grounding bracket, grounding clamp, DC terminal cover grommets, terminal nuts, supply and motor connector, surface mounting brackets, control terminals, relay connectors, 24Vpower supply connector and finger guard grommets

Items supplied with the drive

Capable of meeting the requirements of Equipment Category C3 without external filters or line reactors. Capable of meeting the requirements of Equipment Category C2 when installed with the recommended filters and line reactors. IEC61800-3, EN61000-6-4, EN61000-3-2, EN61000-3-12, EN61000-3-3, EN12015

Emission compliance

Storage temperature

-40°C to 55°C, -40°F to 131°F

Operating temperature without de-rate

-20°C to 40°C, -4°F to 104°F

Cooling

Forced cooled

Operating temperature with de-rate

40°C to 55°C, 104°F to 131°F

Safe Torque off

Single STO. SIL 3

Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance between phases). Input frequency 45 to 66Hz

Supply requirements

RS485 with Modbus RTU EtherNet/IP, EtherCAT, PROFIBUS, PROFINET, DeviceNET, POWERLINK and CANopen via option modules

Communications

Switching frequency range

2,3,4,6,8,12,16kHz (Factory default = 3kHz)

Approvals

CE (European Union), cUL Listed (USA and Canada), RCM (Australia/ New Zealand), EAC (Russian Customs Union), UKCA

2 x analogue input, 2 x analogue outputs, 3 x Digital I/O programmable, 3 x Digital input, 2 x NO relay 250Vac Max., 5 x 0V common, 1 x 24V user output, 1 x 24V external input, 1 x STO input. Additional I/O available with SI-I/O option module.

Control I/O

Product safety standard

EN61800-5-1

Functional safety

Single STO Function

Frequency 0.01%,Analogue input 1 and 2: 11 bits plus sign, Current accuracy typical 2%.

Accuracy

Altitude

1000m – No de-rate. 1000m to 3000m - 1% de-rate/100m

On-Board user program capability

N/A

Humidity

95% Non-condensing

Keypad (LCD)

KI- HOA keypad RTC (real time clock), optional HOA Remote Keypad

Pollution

Degree 2. Dry, non-conducting pollution only

‘Connect’ commissioning and cloning tool including CT Oscilloscope, Machine Control Studio for second processor module programming.

IP Rating

IP20 – Pollution degree 2

PC Tools

Reference standard IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test.

Vibration

Warranty

5 years

Mounting methods

Surface mount or through-panel mount via mounting brackets

HMI, Remote Keypad RTC, SI-I/O, Remote I/O, SI-Encoder (speed feedback), SI-Universal Encoder, MCi200 (second processor), MCi210 (second processor), SI-Ethernet, SI-EtherCAT, SI-DeviceNET, SI-PROFIBUS, SI-PROFINET, SI-POWERLINK, SI- CANopen, KI-485 comms adapter, SD card adapter, SMARTCARD

Supported options

Output frequency/speed range

599Hz

Braking

In-built braking transistor, external resistor required.

Through-hole IP65 (frame 3 to 8) or IP55 (frame 9 to 11) mounting kits, UL type conduit kits, retrofit mounting brackets, external EMC filters and grounding bracket (supplied with the drive)

Accessories

Operating modes

Open Loop Induction Motor V/F, RFC-A (sensorless induction motor) RFC-S (Sensorless, and feedback via option module)

Overload capability

110% for 165s from cold or for 9s from 100% load

Overvoltage category

Evaluated for OVC III.