WWW.CONTROLTECHNIQUES.COM
WWW.CONTROLTECHNIQUES.COM
SPECIFICATION
Concentrations not exceeding levels set in: EN 50178:1998 Table A2 IEC 60721-3-3 Class 3C2
Corrosive environments
IEC61800-3, EN60800-6-2, IEC 61000-4-2, IEC 61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-11, IEC61000-6-1, IEC 61000-6-2.
Immunity Compliance
F600
Step-By-Step Guide, safety information, grounding bracket, grounding clamp, DC terminal cover grommets, terminal nuts, supply and motor connector, surface mounting brackets, control terminals, relay connectors, 24Vpower supply connector, finger guard grommets, IP65 cover and IP65 mounting brackets
Capable of meeting the requirements of Equipment Category C3 without external filters or line reactors. Capable of meeting the requirements of Equipment Category C2 when installed with the recommended filters and line reactors. IEC61800-3, EN61000-6-4, EN61000-3-2, EN61000-3-12, EN61000-3-3, EN12015
Items supplied with the drive
Emission compliance
Storage temperature
-40°C to 55°C, -40°F to 131°F
Cooling
Forced cooled
Operating temperature without de-rate
-20°C to 40°C, -4°F to 104°F
Safe Torque off
Single STO. SIL 3
Operating temperature with de-rate
40°C to 55°C, 104°F to 131°F
Communications
RS485, MODBUS RTU, PROFIBUS, Ethernet, EtherCAT, DeviceNET, CANopen and PROFINET
Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance between phases). Input frequency 45 to 66Hz
2 x analog input, 2 x analog outputs, 3 x Digital I/O programmable, 3 x Digital input, 2 x NO relay 250Vac Max., 5 x 0V common, 1 x 24V user output, 1 x 24V external input, 1 x STO input. Additional I/O available with SI-I/O option module.
Supply requirements
Control I/O
Switching frequency range
2,3,4,6,8,12,16kHz (Factory default = 3kHz)
Frequency 0.01%,Analogue input 1 and 2: 11 bits plus sign, Current accuracy typical 2%.
Approvals
CE (European Union), cUL Listed (USA and Canada), RCM (Australia/ New Zealand), EAC (Russian Customs Union)
Accuracy
Product safety standard
EN61800-5-1
On-Board user program capability
N/A
Functional safety (Dual STO function)
TuV
Keypad (LCD)
KI- HOA keypad RTC (real time clock), optional HOA Remote Keypad
Altitude
1000m – No de-rate. 1000m to 3000m - 1% de-rate/100m
‘Connect’ commissioning and cloning tool including CT Oscilloscope, Machine Control Studio for second processor module programming.
PC Tools
Humidity
95% Non-condensing
Warranty
5 years
Pollution
Degree 2. Dry, non-conducting pollution only
HMI, Remote Keypad RTC, SI-I/O, Remote I/O, SI-Encoder (speed feedback), SI-Universal Encoder, MCi200 (second processor), MCi210 (second processor), SI-Ethernet, SI-EtherCAT, SI-DeviceNET, SI-PROFIBUS, SI-PROFINET, SI- POWERLINK, SI-CANopen, KI-485 comms adapter, SD card adapter, SMARTCARD
IP Rating
IP65
Supported options
Reference standard IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test.
Vibration
Accessories
External EMC filters
Mounting methods
Surface mount or through-panel mount via mounting brackets
Output frequency/speed range
599Hz
Braking
In-built braking transistor, external resistor required.
Operating modes
Open-loop, RFC-A (enhanced open-loop performance) RFC-S (permanent magnet motor)
Overload capability
110% for 165s from cold or for 9s from 100% load
Documentation & Downloads Product documentation and PC tools available for download from: www.controltechniques.com/support
Overvoltage category
Evaluated for OVC III.
144
145
Made with FlippingBook Publishing Software