WWW.CONTROLTECHNIQUES.COM
WWW.CONTROLTECHNIQUES.COM
SPECIFICATION
Overvoltage category
Evaluated for OVC III.
Concentrations not exceeding levels set in: EN 50178:1998 Table A2 IEC 60721-3-3 Class 3C2
Corrosive environments
H300
Step-By-Step Guide, safety information, grounding bracket, grounding clamp, DC terminal cover grommets, terminal nuts, supply and motor connector, surface mounting brackets, control terminals, relay connectors, 24Vpower supply connector, finger guard grommets, IP65 cover and IP65 mounting brackets
Immunity Compliance
IEC61800-3, EN60800-6-2, IEC 61000-4-2, IEC 61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6,
Items supplied with the drive
IEC61000-4-11, IEC61000-6-1, IEC 61000-6-2.
Storage temperature
-40°C to 55°C, -40°F to 131°F
Capable of meeting the requirements of Equipment Category C3 without external filters or line reactors. Capable of meeting the requirements of Equipment Category C2 when installed with the recommended filters and line reactors. IEC61800-3, EN61000-6-4, EN61000-3-2, EN61000-3-12, EN61000-3-3, EN12015
Operating temperature without de-rate
-20°C to 40°C, -4°F to 104°F
Emission compliance
Operating temperature with de-rate
40°C to 55°C, 104°F to 131°F
Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance between phases). Input frequency 45 to 66Hz
Supply requirements
Cooling
Forced cooled
Safe Torque off
Single STO. SIL 3
Switching frequency range
2,3,4,6,8,12,16kHz (Factory default = 3kHz)
- RS485 with Modbus RTU - BACnet MS/TP - EtherNet/IP, EtherCAT, PROFIBUS, PROFINET, DeviceNET, POWERLINK and CANopen via option modules 2 x analogue input, 2 x analogue outputs, 3 x Digital I/O programmable, 3 x Digital input, 2 x NO relay 250Vac Max., 5 x 0V common, 1 x 24V user output, 1 x 24V external input, 1 x STO input. Additional I/O available with SI-I/O option module.
CE (European Union), cUL Listed (USA and Canada), RCM (Australia/ New Zealand), EAC (Russian Customs Union), UKCA
Approvals
Communications
Product safety standard
EN61800-5-1
Functional safety
Single STO Function
Control I/O
Altitude
1000m – No de-rate. 1000m to 3000m - 1% de-rate/100m
Frequency 0.01%,Analogue input 1 and 2: 11 bits plus sign, Current accuracy typical 2%.
Humidity
95% Non-condensing
Accuracy
Pollution
Degree 2. Dry, non-conducting pollution only
On-Board user program capability
N/A, Only via additional MCI200/ 210 Option Module
IP Rating
IP65
Keypad (LCD)
KI- HOA keypad RTC (real time clock), optional HOA Remote Keypad
Reference standard IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test.
Vibration
‘Connect’ commissioning and cloning tool including CT Oscilloscope, Machine Control Studio for On-board PLC programming.
PC Tools
Mounting methods
Surface mount or through-panel mount via mounting brackets
Warranty
5 years
Output frequency/speed range
599Hz
HMI, Remote Keypad RTC, SI-I/O, Remote I/O, SI-Encoder (speed feedback), SI-Universal Encoder, MCi200 (second processor), MCi210 (second processor), SI-Ethernet, SI-EtherCAT, SI-DeviceNET, SI-PROFIBUS, SI-PROFINET, SI- POWERLINK, SI-CANopen, KI-485 comms adapter, SD card adapter, SMARTCARD
Braking
In-built braking transistor, external resistor required.
Supported options
Open Loop Induction Motor V/F, RFC-A (sensorless induction motor) RFC-S (sensorless, and feedback via option module)
Operating modes
Through-hole IP65 (frame 3 to 8) or IP55 (frame 9 to 11) mounting kits, UL type conduit kits, retrofit mounting brackets, external EMC filters and grounding bracket (supplied with the drive)
Accessories
Overload capability
110% for 165s from cold or for 9s from 100% load
Documentation & Downloads Product documentation and PC tools available for download from: www.controltechniques.com/support
162
163
Made with FlippingBook Publishing Software