Control Techniques - Comprehensive Catalogue

WWW.CONTROLTECHNIQUES.COM

WWW.CONTROLTECHNIQUES.COM

SPECIFICATION

Power & Control

Mounting & Environment continued Cooling

100 V drive: 100 V to 120 V ±10 % 200 V drive: 200 V to 240 V ±10 % 400 V drive: 380 V to 480 V ±10 % 575 V drive: 500 V to 575 V ±10 % 690 V drive: 500 V to 690 V ±10 % Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance between phases)

Integral cooling fan

Altitude

≤3000 m (≤1000 m no de-rate; 1000 m to 3000 m derate 1 % every 100 m)

Supply Requirements

Humidity

95 % non-condensing at 40 °C / 104 °F - EN61800-2(3k3)

Pollution

Pollution degree 2 - dry, non-conducting pollution only

Input Displacement Power Factor

0.97

Reference standard IEC60068-2-27, IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test. Tested to Environmental Category ENV3

Vibration

Phase

1 and 3 (model dependent)

Mechanical Shock

Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29

Power Range

0.25 to 132 kW / 0.33 to 200 hp

Input Frequency Range

45 to 66 Hz

Frame 1 to 4 – Surface mount via mounting holes or DIN Rail mount Frame 5 to 9 – Surface mount via mounting brackets or through-panel mount via through-panel mounting kit

Mounting Methods

Output Frequency/Speed Range

0 to 550 Hz

Size 1 - 4: 0.667, 1, 2, 3, 4, 6, 8 12 & 16 kHz Size 5 - 9: 2, 3, 4, 6, 8 12 & 16 kHz (Factory default = 3kHz)

Mounting Clearance

0 mm either side, 100 mm above and below

Switching Frequency

Overvoltage Category

Category III (IEC/EN/KN/UL 61800-5-1)

Heavy Duty Overload Capability

150 % for 60 s (open loop mode), 180 % for 3 s (RFC-A mode)

Corrosive Environments

EN 60721-3-3 ISO9223 Class C3

Linear V to F Square V to F

75 m Frame 1 100 m Frames 2 to 4 200 m Frames 5 to 6 250 m Frames 7 to 9

Dynamic V to F Set Point V to F Stator Resistance Compensation RFC-A (enhanced open-loop performance)

Operating Modes

Maximum Motor Cable Length

Standards

Coast, Ramp, Ramp & DC Injection Braking, DC Injection Braking with 0 Hz detect, Timed DC Injection Braking Built-in braking transistor, external resistor required

Stopping Modes

CE (European Union), cUL Listed (USA and Canada), DNV (marine applications), KC (Korea), RCM (Australia/ New Zealand), EAC (Russian Customs Union), UKCA (United Kingdom), C-Tick (Australia)

Approvals

Communication & Interfaces

Modbus RTU, EtherCAT, PROFIBUS, Ethernet, DeviceNET, CANopen, PROFINET, POWERLINK (all available with AI/SI-options)

E171230

Communications

Product Safety Standards

IEC/EN/KN/UL 61800-5-1, CSA C22.2 No.274, GB12668.501-2013

Fixed LED keypad Remote IP66 Keypad (available as an accessory) Remote IP66 RTC Keypad (available as an accessory) HMI (available as an accessory) Connect (PC commissioning & cloning tool) Machine Control Studio for on-board PLC programming

C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine. Type examination certificates by TÜV Rheinland:

Keypads

Frame sizes 1 - 4: No. 01/205/5383.03/18 Frame sizes 5 - 9: No. 01/205/5387.02/18 Functional safety parameters: EN ISO 13849-1 - Cat 4, PLe EN61800-5-2/EN62061/IEC 61508 - SIL 3 UL functional safety approval: FSPC E171230

TÜV

User Software Tools (Free To Download)

Inputs & Outputs

2 x Analogue input Possible settings: 0-10 V, 0-20 mA, 4-20 mA (No Alarm), 4-20 mA (Alarm), 4-20 mA (Error)

IEC/ EN 61800-3 Immunity and Emissions EN 61000-6-2: Immunity for industrial environments EN 61000-6-4: Emissions for industrial environments

Analogue

1 x Analogue output Possible settings: 0-10 V

Product EMC Standards

EN 61000-3-2: Harmonic current emissions An EMC data sheet is available on request

3 x Digital inputs (1 frequency input) 1 x Digital input / output programmable 1 x Digital input / output programmable (can be used as a frequency or PWM output to represent analogue value)

Digital

RoHS

Complies with the Restriction of Hazardous Substances Directive (2011/65/EU)

Digital Input Logic

Positive

Immunity Compliance

Second environment (Industrial)

Relay

1 x Relay (single pole, double throw relay)

ISO

Manufacturing facilities comply with ISO 9001:2015 and ISO 14001

Accuracy

Frequency 0.02%,Analogue input 1: 11 bit plus sign,Analogue input 2: 11 bit. Current typical 2%.

Warranty Warranty

3 x Analogue inputs (default) / Digital inputs programmable 4 x Digital input / output programmable 1 x Digital input 2 x Relays

5Years (warranty terms and conditions apply)

Extra I/O with SI-I/O Option Module (Available as an Accessory)

Accessories

Remote Interfaces

Remote keypad IP66, Remote keypad RTC, HMI

Mounting & Environment

IP20 Conduit Box UL Type 1 ingress protection (available as an accessory)

Filters & Cables

External EMC filters, CT communications cable

IP Rating

AI-485 24 V Adaptor, SI-EtherCAT, SI-PROFIBUS, SI-Ethernet , SI-DeviceNET, SI-CANopen, SI-PROFINET , SI-POWERLINK, SI-Encoder

Storage Temperature

-40 °C to 60 °C (-4 °F to 140 °F)

Communication & Feedback, SI-Options

Operating Temperature Without De-Rate

-20 °C to 40 °C (-4 °F to 104 °F)

-20 °C to 60 °C (-4 °F to 140 °F) Frames 1 to 4 -20 °C to 55 °C (-4 °F to 131 °F) Frames 5 to 9

Operating Temperature with De-Rate

50

51

Made with FlippingBook Publishing Software