When determining the proper duct size the equivalent length for bends must be used.

90 - degree Bend (Figure 4) A 90 - degree bend has pressure drop equal to approximately twenty (20) lineal feet of flexible duct.

45 - degree Bend (Figure 5) A gradual 45 - degree bend has pressure drop equal to about ten (10) lineal feet of flexible duct.

180 - degree Offset (Figure 6) A 180 - degree offset has pressure drop equal to about forty (40) lineal feet of flexible duct.