ADC GreenBook 6th Edition - JPL

6

CHAPTER 6: ADC TEST STANDARDS

6.1

Performance Values

Table 1 lists the required tests and units of measurement and recommended values of minimum performance where applicable.

For comparison purpose only. Not for design. For detailed design data, refer to manufacturer ’ s product engineering data.

Property

Recommended Performance Value

R: hr·ft 2 ·°F/BTU [(m 2 ·°C/W]

Thermal Loss* All diameters

Test - Section 6.2.1 - Thermal Performance

4.2 [0.74](minimum) @ 75°F [24°C] mean temperature

Friction Loss 12" [300 mm]

Straight:(in.w.g. per 100 ft. [Pa/m] of duct @ 1000 fpm [5.1 m/s])

Test - Section 6.2.2 - Friction Loss

0.3 [2.5] (maximum)

diameter

90° bend loss coefficient (C o )

1.0 (maximum)

@ R/D = 2

26

Acoustical

Sound Attenuation Sound Generation

Test - Section 6.2.3 - Acoustical Performance Due to complexity of data, no recommended value of performance is stated. Refer to Manufacturer ’ s Data.

(dB)

Radiated Noise

Static Press./Temp

At Recommended Operating Positive Pressure (in. w.g.) [Pa]

Test - Section 6.2.4 - Static Press./Temp. Performance

12" [300 mm]

140° F [60° C] Continuous 180° F [82° C] Intermittent

diameter

Leakage

cfm/in. (dia.)·ft. (length) [L/s/mm (dia.)·m (length)]

Test - Section 6.2.5 - Duct Leakage

0.03 [1.7 x 10ˉ 4 ]

All diameters

Leakage

cu.ft./hr. [L/s]

Test - Section 6.2.5 - Duct Leakage (Including

Connections) All diameters

0.87 [1.1 x 10ˉ 5 ] D 2 (maximum) where D is internal duct diameter in inches [mm].

U.S. Perms [ng/(s·m 2 ·Pa)]

Permeance* All diameters

Test - Section 6.4.1

Water Vapor Transmission Rates of Vapor Barriers 1.0 [57.5] (maximum)

* Not applicable to uninsulated ducts.