B

APPENDIX B

UL 181 TEST SECTIONS

Test

Air Ducts

Air Connectors

Surface Burning Characteristics 1

x

x

Flame Penetration

x

-

Burning

x

x

Corrosion a

x

x

Mold Growth and Humidity

x

x

Temperature

x

x

Puncture

x

-

x b

x b

Static Load

Impact

x

-

Erosion 2

x

x

Pressure 2

x

x

Collapse 2

x

x

33

Tension

x

x

Torsion

x

x

Bending

x

x

Leakage

x

x

Listing Label Shape

Rectangular

Round

X

Test applicable

-

Test not applicable

a

Applicable to parts of metals not inherently corrosion resistant.

b Test applicable for flexible air ducts and air connectors that incorporate vapor barriers supported by grommets or other means of field support.

Footnote 1 Tests for surface burning characteristics are to be conducted as specified for Surface Burning Characteristics of Building Materials, UL 723 (ASTM E84, NFPA 255).

Class 0 Material: Shall have surface burning characteristics of zero (flame spread/smoke developed).

Class 1 Material: Shall have flame spread rating of not over 25 without evidence of continued progressive combustion and a smoke - developed rating of not over 50.

Footnote 2 These three tests, Pressure, Erosion and Collapse, are run at 2.5 times the manufacturer ’ s stated rating for that property. For the erosion test, the variable is velocity; for the pressure test the variable is positive pressure; for the collapse test, the variable is negative pressure.