A - Alto-Shaam - Converge Multi-Cook Oven

Converge® Multi-Cook Oven

Top:

20" (500mm)*

• The oven must be installed level. • Water supply shut-off valve and back-flow preventer when required by local code. • Drain must not be located directly underneath the appliance. • Oven not intended for built-in installation.

Left:

2" (51mm)

Right:

2" (51mm)

Front:

20" (508mm)

CLEARANCE

CHECK FIRST

Back:

7-1/16" (179 mm)

* 18" (457mm) recommended for service access

Heat of rejection

Noise emissions Without hood system, a maximum 63.3 dBA was measured at 3.3 ft (1 m) from unit.

Heat Gain qs, BTU/hr 471 706

Heat Gain qs, kW

CMC-H2H CMC-H3H

0.14 0.21

HEAT

NOISE

Water requirements (per oven) • Two cold water inlets - drinking quality

Water Quality Standards It is the sole responsibility of the owner/operator/purchaser of this equipment to verify that the incoming water supply is comprehensively tested and, if required, a means of “water treatment” provided that would meet compliance requirements with the published water quality standards shown below. Non-compliance with these minimum standards will potentially damage this equipment and/or components and void the original equipment manufacturer’s warranty. Alto-Shaam recommends using the Alto-Shaam Reverse Osmosis System to properly treat your water.

• One treated water inlet: 3/4” NPT male connection. Line pressure 30 psi (200 kPa) minimum dynamic and 145 psi (1000 kPa) maximum static–at a minimum flow rate of 0.16 gpm (0.6 L/min). • One untreated water inlet: 3/4” NPT male connection. Line pressure 30 psi (200 kPa) minimum dynamic and 145 psi (1000 kPa) maximum static at a minimum flow rate of 4 gpm (15 L/min). • Water drain: 1-1/2” (40mm) connection with a vertical vent to extend above the exhaust vent. Materials must withstand temperatures up to 200°F (93°C). • Water supply connections to be 3/4” NPT male fittings.

WATER

Inlet Water Requirements

Contaminant Treated Water

Untreated Water

Free Chlorine

Less than 0.1 ppm (mg/L)

Less than 0.1 ppm (mg/L)

Hardness

30–70 ppm

30–70 ppm

Chloride

Less than 30 ppm (mg/L)

Less than 30 ppm (mg/L)

Clearance requirements for water filtration system Do not install a water filtration system behind unit.

pH

7.0 to 8.5

7.0 to 8.5

Silica

Less than 12 ppm (mg/L)

Less than 12 ppm (mg/L)

Total Dissolved Solids (tds)

50–125 ppm

50–360 ppm

CLEARANCE

W164 N9221 Water Street | Menomonee Falls, Wisconsin 53051 | U.S.A. Phone: 262.251.3800 | 800.558.8744 U.S.A./Canada | Fax: 262.251.7067 | alto-shaam.com

CONTACT US

CMC-SPC-0001 - 9/24

Printed in U.S.A. Due to ongoing product improvement, specifications are subject to change without notice.