Catalog No. 1044A TESCO 20 Amp Current Transformer Burden Test Set
Catalog No.1044A (20) Amp CT Burden Test Set is a lightweight, handheld unit. The 1044A provides a simple and inexpensive means whereby a current transformer installation may be quickly checked for many sources of trouble. The 1044A provides utilities a less expensive and more traditional option for checking larger services for potential meter circuit related issues. Extensive precautions have been taken in the design of the CT Burden Test Set. A continuous and closed path in the watt-hour meter current circuit exists at all times, and the secondary of the current transformer will not open by accident. Specifications: • Current Ranges: 1.5, 2.5, 5, 10, 20 amperes • Burden Values: 0.1, 0.2, 0.5, 1.0, 2.0, 4.0, 8.0 ohms • Readability: The meter is a 2.5” panel instrument with a scale of 2 3/16” and a transparent unbreakable plastic cover for easy viewing. • Duty Cycle: The instrument is rated for continuous duty up to the largest current value except for the burden resistors which are rated for intermittent duty. • Dimensions: 7.5” x 8.5” x 3.125” (W x H x D) • Weight: 3.5 lbs. Accessories: • Carrying Case, Catalog No. 1046D - Overall Size: 8.5” x 9” x 5” (W x H x D) - Weight: 1 lb. • Test Plug, Catalog No. 1077 • Optional Leads - J-35-50C 6 ft. cable with copper clips - J-35-50T 6 ft. cable with Catalog No. 1077 Test Plug
CURRENT TRANSFORMER BURDEN TEST SET CATALOG NO. 1044A
TESCO Metering 925 Canal Street · Bristol, PA 19007 · Phone: 215.228.0500 tescometering.com