Fire Pull The fire pull is used for the manual activation of the fire suppression system. These are typically mounted remotely so that cell operators can activate them in emergency situations. The fire pull will be mounted on the front of the electrical door. A key is used to reset the fire pull once it has been activated, and a glass tube can be inserted to detect an activation that has been reset. To reset the fire pull, the power must be turned off before the fire pull has been reset. The internal program of the Smart Relay latches shut
electronically, forcing the power to be cycled off and then on. If the fire pull has been activated, the display will show “FPull” as shown in the picture below. NOTE: On Synapse panels, the fault must also be cleared on the HMI by pressing the “Reset FSS” button on the fire suppression screen.