Additional Sprinkler On the motor compartment side, on the top right of the unit, a ½” pipe can be found hanging out of the unit. This pipe routes to the filter compartment side. This pipe allows for additional water sprinkler to be added to the unit to help extinguish fire and needs to be connected to water supply.
F IRE S UPPRESSION P ROCEDURE In the event of a fire in the filter compartment of the dust collector, follow the following steps: NOTE: Shutting off power to the unit if a fire is detected will cause the suppression system to stop working. 1)Initial Detection If your unit is equipped with Automatic Fire Suppression, the system is running, and the system is functioning properly, the fire will be detected by the smoke sensor AND/OR primary heat detector. The system will block the airflow, shut down the power to the motor controls, activate the strobe/horn, and stop the valves from pulsing. If the primary heat detector has been activated, then the fire bottle will discharge after 30 seconds. The activating device should be indicated on the panel display.