7) Inspect The suppression agent leaves a dust layer. The filters can then be inspected for damage and further extinguished as required. Some or all filters will most likely need to be replaced. Please inspect your unit for possible damage before reinstalling undamaged filters. 8)Restart Turn the key switch to the off position to temporarily deactivate the FSS to prevent initial false alarms due to contamination beyond the filters. Turn on the main power and cycle the unit power disconnect from off to on. This will reset the system. Check to be sure the unit’s smoke detectors are showing green flashing lights. Run the unit for a short period of time to purge any residual smoke. Clean the smoke detector with compressed air if required. Once the unit has been cleaned, the key switch can be turned to the on position to reactivate the FSS and allow proper detection. This may take several cleanings. 9)Reset

If using a Synapse panel, reset the fire suppression fault on the fire suppression screen.

10) Install the Replacement Generator

In the filter compartment, disconnect the suppression agent generator and remove it from its mount. Install the new generator in its place and re-terminate the control wiring on the new generator. 11) Normal Operations Return to normal operation. Inspect hood pick up point system to determine a corrective action to minimize the opportunity for an ignition source reaching the filters. The fire suppression behavior is noted in Table 1 below: Table 1: