21) It may take a few minutes for the heat detector to cool down. 22) Turn power back on at the Disconnect. 23) If using a synapse panel, make sure to press the reset FSS button under the fire suppression screen. 24) Repeat steps 17 – 23 for the second secondary detector if it is present. 25) Turn power back on at the Disconnect. 26) Use a can of smoke or lit cigarette to activate the smoke detector located in the valve compartment. The behavior should follow the process noted in Table 1. This verifies the smoke detector is working. Make sure the power is applied to the terminals to activate the suppression agent generator. 27) Turn power off at the Disconnect. 28) The smoke detector may need to be blown out with compressed air to reset. 29) Turn power back on at the Disconnect. 30) If using a synapse

panel, make sure to press the reset FSS button under the fire suppression screen. 31) Repeat steps 26 – 30 for the second primary detector if it is present. 32) Reconnect the wiring connection in junction box inside the valve compartment for the suppression agent generator(s). Failure to do so will prevent discharge of the fire suppression agent.