FIRE PROTECTION - END SUCTION PUMPS
Cast iron pump casing with centerline discharge, hydraulically engineered to yield best in class efficiency, does not retain air, eliminates need of separate air venting accessories as there are no air pockets within pump casing
Double shrouded impeller is provided with vanes on back shroud to balance axial thrust, larger impeller use dual wear ring with balance holes
Back pull out design allows removal of rotating assembly and bearing housing without disturbing suction and discharge piping
Impellers are specifically designed to meet NFPA 20, UL:448, FM:1319 fire pump requirementes
Design conforms to DIN:24255, ISO:2858 and ISO 5199, which is modular and interchangeable parts, fewer spares needed
Sturdy, yet simple, bearing is designed to withstand bi axial loads without having to use expensive angular contact bearings
Flanges drilled per ANSI B 16.1, optional drillings available per request
CONFIGURATION Horizontal electric motor or engine driven
FEATURES • Horizontal DIN 24255 electric motor • 41 models • Wide choice of materials • Centreline discharge • Back pull-out rotating element can be removed without disturbing pipe work • Impellers cut to duty • High interchangeability – just three shaft modules cover the entire range
• Suitable for baseplate mounting with coupling • Approved to LPCB, FM and/or UL standards • In compliance with NFPA 20 • Used in pump as turbine applications
DISCHARGE & PERFORMANCE  • 1.25 in. to 6 in. • Outputs up to 2200 gpm • Heads up to 345 ft.
FIRE - END SUCTION PUMPS
Made with FlippingBook - professional solution for displaying marketing and sales documents online