Liberty Weld Cell User & Maintenance Manual

F IRE S UPPRESSION P ROCEDURE

In the event of a fire in the filter compartment of the dust collector, follow the following steps:

NOTE: Since January 2020, Clean Air Industries has redundant fire detecting system which will trigger the fire agent regardless of power status. However, it is highly recommended not to shut off power during

fire to allow the whole fire suppression system to work together.

1) Initial Detection

If your unit is equipped with Automatic Fire Suppression, the system is running, and the system is

functioning properly, the fire will be detected by the smoke sensor AND/OR heat detectors. The

system will block the airflow, shut down the power to the motor controls, activate the strobe/horn, and

stop the valves from pulsing. If the primary heat detector has been activated, then the fire bottle will

discharge after 20 seconds. The activating device should be indicated on the panel display.

2) Secondary Detection

If the smoke sensor has tripped, but not a heat sensor, air flow should stop and heat should build up in

the filter compartment. This will cause the secondary heat sensors to trip.

Caution:

In the case of filter misalignment, the smoke sensor will trip, but the heat

sensor will not. This is due to smoke bypass.

3) Tube Heat Detection

If fire is present in the filter compartment, the temperature will rise and melts the tubing and cause the

pressure drop in the tubing. This will trigger the release the fire suppression agent immediately.

4) Manual Detection

If the unit is still operating, immediately locate the manual fire suppression system Fire Pull. Operate

the switch by pulling the lever downward to engage the fire suppression system. The system will block

the airflow, shut down the power to the motor controls and turbo controller, and fill the filter

compartment with suppression agent after 20 seconds.

5) Alert

For safety, immediately follow your plant specified Fire Plan. The system is NOT tied into the plant fire

protection system by Clean Air Industries . Alert officials!

Copyright © Clean Air Industries , Inc.

Liberty WeldCell User Manual, August 2023

Page 33 of 66

Made with FlippingBook - PDF hosting