Once you have verified that the Liberty Weldcell is picking up the fumes or smoke, look at the

metal intake spark baffles at the back of the welding booth(s). These filters should be washed

when they become visibly dirty/contaminated.

If the unit begins auto pulsing at 7.0 in. H 2 O and the smoke is still being drawn in at an

acceptable level, the setting could be increased to a higher number. The correct number is

based on trial and error.

The process for determining your specific filter change interval is based on many variables.

Please feel free to establish a filter change interval that meets you application and desired

performance results. By properly monitoring the filters you will reduce filter costs and improve

the efficiency of the units.

Proper filter cartridge replacement is important to optimal performance of the Liberty

Weldcell.

What determines the maximum acceptable pressure

differential reading?

The answer is a reading slightly less than the point where the unit stops drawing in an

acceptable level of smoke plume.

If the unit still draws acceptably at 7.0 in. H 2 O, then the controller can be set to begin the auto

pulse cycle at a higher level. Please see the controller programming instructions for this

procedure.

If the unit stops draws acceptably at 5.0 in. H 2 O, then the controller can be set to begin the

auto pulse cycle at a lower level. Please see the controller programming instructions for this

procedure.