Fluke Australia 2020 Test Tools Catalogue

Fluke 1630-2 FC Earth Ground Clamp Meter

Stakeless earth ground loop and AC leakage current clamp for fast, safe indoor/outdoor earth ground resistance and AC leakage current tests. Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments. Test the grounding components of equipment in hard- to-reach spaces, including areas that are indoors or fully paved and do not permit driving auxiliary test stakes. Stay on line—identify ground loop resistance without the need to disconnect then reconnect the earth electrode from the system. Stakeless measurement The 1630-2 FC clamp measures earth ground loop resistances for multi-grounded systems using the dual- clamp jaw. This test technique eliminates the dangerous and time-consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary test stakes. You can also perform ground tests in places that were previously difficult: inside build¬ings, on power pylons or anywhere you don’t have access to soil to place auxiliary test stakes. With this test method, a two- process measurement is made around the earth ground wire or bus bar using the specially-designed jaw of the 1630-2 FC clamp. Auxiliary test stakes are not used at all. A known voltage is induced by the source in the clamp, and the current is measured by the sensor in the clamp. The tester automatically determines the earth loop resistance for this section of the earthing system. One year warranty.

Ground Resistance Measurement Principle

Equivalent Circuit Diagram

Fluke 1630-2 FC

Electrical specifications Maximum voltage to earth ground

1000 V

Battery type Battery life

4 x 1.5 V AA alkaline IEC/EN LR6

More than 15 hours

Frequency range Ingress protection

40 Hz to 1 kHz

IEC/EN 60529: IP30 with jaw closed

LCD

Digital reading

9999 counts

Refresh rate 4/s

Reference temperature Display Reading Specification with Loop Resistance Standard

23 °C ±5 °C

Input (Ω)

Minimum

Maximum

0.474

0.417 0.443

0.531 0.558 10.45 104.0

0.5

10

9.55

100

96

Data logging capacity

Minimum of 32,760 measurements

Safety

General IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1 Measurement IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V

Current clamp for leakage current measurements

IEC/EN 61557-13: Class 2, ≤30 A/m

Resistance to Earth Effectiveness of the protective measures

IEC/EN 61557-5

Included Accessories

IEC/EN 61557-16: cutoff frequency 20 kHz (-3 dB)

Hard Case, Loop Resistance Standard, Four AA Batteries, Safety Information Guide and Quick Reference Guide.

General specifications Conductor size Dimensions (L x W x H)

40 mm approximately

283 mm x 105 mm x 48 mm

Weight

880 g

Ordering Information

Fluke-1630-2 FC Earth Ground Loop and Leakage Clamp

C ontact your local distributor for price and availability. www.fluke.com/au/wtb

www.fluke.com/au/EGT

Earth Ground Testers

79

Made with FlippingBook Learn more on our blog