Complete Arch Manual

MajO 07.25.21 Div

Cabinet Specifications

Cabinet Specifications

SECTION 12 35 53.19 – WOOD LABORATORY CASEWORK PART 1 GENERAL 1.01 SUMMARY A. Section Includes:

COMPLIANCE STATEMENT – SECTION 12 35 53.19

Project: Bidding Company: INSTRUCTIONS:

1. All cabinets and casework, including tops, ledges, supporting structures, and miscellaneous items of equipment as listed in these specifications, or equipment schedules including delivery to the building, setting in place, leveling, scribing to walls and floors as required. Furnish and install all filler panels, knee space panels and scribes as shown on drawings. Installation shall be completed by a factory certified installer. 2. Furnish and deliver all utility service outlet accessory fittings, electrical receptacles, and switches, as listed in these specifications, equipment schedules or as shown on drawings as mounted on the laboratory furniture. Items shall be furnished with supply tank nipples and lock nuts, loose in boxes and properly marked. All plumbing and electrical fittings will be packaged separately and properly marked for delivery to the appropriate contractor. 3. Furnish and deliver, packed in boxes for installation by the mechanical contractor, all laboratory sinks, cup sinks or drains, drain troughs, overflows and sink outlets with integral tailpieces, which occur above the floor and where these items are part of the equipment or listed in the specifications, equipment schedules or shown on the drawings. Integral tailpieces when required shall be in accordance with the manufacturer’s standards. All tailpieces shall be furnished less the couplings required to connect them to the drain piping system. 4. Furnish service strip supports and set in place service tunnels, service turrets, supporting structures and reagent racks of the type shown on the details. 5. Remove all debris, dirt and rubbish accumulated as a result of the installation of the laboratory casework to an onsite container provided by others, leaving the premises clean and orderly. B. Related Divisions: 1. Divisions 05 00 00 & 06 00 00: Behind-the-Wall Blocking and Studs 2. Division 09 00 00: Base Molding 3. Division 11 53 13: Chemical Fume Hoods 4. Division 22 00 00: Plumbing 5. Division 26 00 00: Electrical Fittings and Connections C. Related Publications: 1. Architectural Woodwork Institute Quality Standards, 8th Edition

This Compliance Statement is to ensure all bids are comparable products and meet specifications. Initial each item in appropriate column and sign at bottom. Submit completed statement with bid. Non-compliance and lack of completed Compliance Statement are cause for dismissal of bid.

YES

NO

1.

Lifetime warranty

2.

Mechanical fastening at front toe base

3. AWI Premium hardwood dowel cabinet joinery - 64mm on center

4.

MAS® or GreenGuard® Certified

5. HPVA Grade A-1 plain-sliced veneers, vertically matched

6.

Independently tested to SEFA 8W

7.

Stainless steel five-knuckle institutional hinges

8.

Screws strips at top and bottom of wall cabinets

9. Chemical-resistant finish meets AWI standards and is applied to parts prior to assembly via a flat line, roller applied system 10. Chemical-resistant finish meets SEFA standards and is VOC-free

11. Cabinets will be foam and shrink-wrapped, not blanket wrapped

2. NFPA 30 – National Fire Protection Association 3. NFPA-45 - National Fire Protection Association

Our bid is for cabinets built per this compliance statement and the specifications as written.

4. UL - Underwriters Laboratory 5. ASTM D552 - Bending Test 6. SEFA 8 W – Laboratory Furniture

Officer of the Bidding Company:

1.02 BASIS OF WORK A. This specification uses Diversified Casework (www.diversifiedcasework.com) Majestic Series (reveal overlay) OAK Cabinetry as the standard of construction for wood laboratory casework. The construction standards of this product line shall provide the basis for quality and functional installation. Pricing from other manufacturers must be submitted as an alternate in order to assure quality standards are maintained. B. Supply all equipment in accordance with this specification. No alternates, deviations or exceptions to the specified construction or materials are allowed. C. As a means of maintaining the desired level of quality, any and all other manufacturers shall be submitted as an alternate to the specified product provided by Diversified Casework.

Signature

Printed

Title

Date

END OF SECTION

12 35 53.19 Wood Laboratory Casework

12 35 53.19 Wood Laboratory Casework

22

DiversifiedCasework.com | info@DiversifiedCasework.com | 877.348.9663

DiversifiedCasework.com | info@DiversifiedCasework.com | 877.348.9663

23

Made with FlippingBook interactive PDF creator