Electronic climate controller, KTRRB Surface-mounted installation – Design Berlin 3000

Technical data

Application

Design:

Berlin 3000

Single-room temperature controller with neutral zone for 2-pipe or 4-pipe air conditioners. External flow sensor (H/C sensor): For automatically switching the controller to heating or cooling mode in 2-pipe operation depending on the inflow temperature; alterna- tively, this input can be used as an H/C changeover contact. Sensor rupture and short-circuit protection: In case of a sensor rupture or sensor short-circuit, the heating is activat- ed with a power-on time of 30% to prevent cooling or frost damage in the room.

Surface finish: Housing colour: Housing material: Operating voltage:

matt

pure white, like RAL 9010

ABS plastic

230 VAC, 50 Hz

Ambient temperature: Storage temperature: Permissible atmospheric humidity: Electrical connection: Mounting/attachment:

0 … 40 °C

−20 … +70 °C

max. 95% rel. humidity, non-con- densing

screw-type terminals

surface-/wall-mounting or by means of an adapter plate on a flush-mount- ed socket

Protection rating: Protection class: Safety and EMC:

IP 30

II, if properly mounted

according to DIN EN 60730

Max. switching voltage: Min. switching voltage:

230 VAC, 50 Hz 230 VAC, 50 Hz

Switching element: Switching contact:

relay

NO contact

Output signal:

switching (230 VAC, 50 Hz)

Sensor:

internal NTC, optional external NTC “Sensor 2” reduction by 3 K; alternatively, this input can be configured as a frost protection contact

ECO contact*:

Control function: Control range:

heating and/or cooling

5 … 30 °C approx. 2 K

Neutral zone:

General features:

operating mode “off with frost protec- tion monitoring”; mechanical range restriction; scale: degrees Celsius; external setting

Type/image

Item no.

Features

PG

KTRRB-117.128

General features: single-room climate controller, 3-stage fan output, fan operation in neutral zone ON/OFF selectable; on/off switch; 3-stage fan switch

MA601300

I

Max. switching current: heating 5 (1) A, cooling 5 (1) A, fan 3 (1) A Switching power: Heating 1150 W, cooling 1150 W, fan 230 W Hysteresis: Approx. 1 K

KTRRB-117.163

MA601400 like KTRRB-117.128 but without 3-stage fan output and 3-stage fan switch

I

KTRRB-117.169

General features: Single-room climate controller; “off/manual fan/automatic fan” switch; “ventilator 3-stage 0–10 V” switch; “parametrisation 3-stage fan output” button; “heating, cooling, frost protection, sensor rupture or short circuiting of the external sensor” display; 3-stage fan output 0–10 V with adjustment to individual fan stages or dynamic 0–10 V to activate EC fans ; ON/OFF: ventilator operation in neutral zone selectable Max. switching current: heating 5 (1) A, cooling 5 (1) A Switching power: Heating 1150 W, cooling 1150 W Output signal: Analogue 0 … 10 V (5 mA) for activating an rpm-controlled fan Hysteresis: Approx. 0.5 K

MA601500

I

Accessories: Adaptor plate for mounting on flush-mounted socket JZ-17, terminal strips VOOxx (see page 107/141), compatible valve actuators ZBOOA (see page 144), compatible external sensors (“Sensor 2”; see “Sensor Technology”). You can find other/similar controllers with outputs for heating/cooling in the “Heating technology” section (RTBSB/RTBSU).

*With ECO operation, the neutral zone (2 K) is extended by the ECO zone (+/- 3 K). ECO operation is a savings mode that should be controlled, for example, via a window contact and/or a timer.

Catalogue 2022 | Page 118