PRODUCT CATALOGUE 2022 | alre.de

Electronic climate controller for cooling ceilings, KTRRB Surface-mounted installation – Design Berlin 2000 – with internal and external (optional) temperature sensor

Technical data

Application

Design:

Berlin 2000

Temperature controller for cooling ceilings/walls and all kinds of hot water heaters in 2- and 4-pipe sys- tems for hotels, offices and private homes. As the KTRRB features dew point monitoring, it is highly suited for controlling ceiling cooling systems. The unit can control up to 5 valve actuators (24 V~ normally closed) per output. The types KTRRB-052.24x can be adapted to normally open actuators (24 V~, max. 5 pieces) with a jumper.

Surface finish: Housing colour: Housing material:

matt

pure white, like RAL 9010

ABS plastic 0 … 40 °C

Ambient temperature: Operating voltage: Storage temperature: Permissible atmospheric humidity: Electrical connection: Mounting/attachment:

24 VAC/50 Hz, 24 VDC

−20 … +70 °C

max. 95% rel. humidity, non-condensing screw-type terminals Surface-/wall-mounting

Protection rating: Protection class: Safety and EMC:

IP 30

III

When using 0–10 V actuators: KTRVB-052.24x.

according to DIN EN 60730

Max. switching current: Max. switching voltage: Min. switching voltage:

1 A

24 VAC/50 Hz, 24 VDC 24 VAC/50 Hz, 24 VDC

Switching power: Switching element: Switching contact:

24 W relay

NO contact

Output signal:

Switching, 24 VAC/50 Hz, 24 VDC NTC internal, optional external, “Sensor 2”*

Sensor:

Hysteresis:

approx. 1 K

General features:

External dew point sensor connec- tion; mechanical range limitation; external setting

Type/image

Item no.

Features

Circuit diagram

PG

KTRRB-052.244

General features: ECO function; “heating/cooling/ cooling interruption due to condensation/off” display; “sensor rupture, sensor short-circuit, frost protection” display; relative scale External flow sensor (H/C sensor): For automatic switching of the controller in heating or cooling mode depending on the inflow temperature (“Sensor 2”). Alternatively, this input can be used as an H/C changeover contact Eco contact: Upon closing the contact, the ECO function is actuated Forced switch-off contact: External switch-off function with frost protection function Control function: heating and/or cooling, cooling interruption upon condensation of the dew point sensor, frost protection function in the switched-off condition Control function: 13 … 29 °C Setting range: −8 … +8 °C Neutral zone: Approx. 2 K Pipe system compatibility: 2-pipe and 4-pipe

DA420600

see page 122

I

Catalogue 2022 | Page 120